7FRCC.ES.010.A4.02
Manual Controller Installation
Electrical installations
Commissioning
Main display (after controller
start-up)
Parameter Menu
Quick start of the unit /
Refrigerant change
Arrange electrical connections as mentioned in the table below
Remove temporarily bridge DI1 (terminals 24 - 25 of the controller) to get access to parameters and
values of the controller without starting the condensing unit
The controller’s screen displays the Evaporation Temperature in °C
Press short the lower button of the controller to show the Condensing Temperature in °C
After a few seconds the display returns to the Evaporation Temperature in °C
To get access to parameter menu press 5 seconds the upper button of the controller
The rst Parameter “r05” of the Parameter menu will be shown on the display
Press short the upper (or lower) button to go to the next Parameter of the Parameter menu. Scroll fast
through the Parameters with a long press on these buttons
Press short the middle button to show the value of the selected Parameter
Press afterwards the upper (or lower) button to change the value of the selected parameter. A long
press on these buttons will change the value fast
The value will be stored after 20 seconds without any action or with a short press on the middle button
After 20 seconds without pressing any button, the display returns to the main screen, the evaporation
temperature in °C. The parameter menu is closed now, to go back to the parameter menu press again
upper button 5 seconds …
Optyma Plus™ new generation is preset, depending on the compressor model and refrigerant type.
In the case of a “multi-refrigerant” compressor, the controller of the condensing unit is set for R404A
(see table on page3). If this factory setting ts for the requirement of your application, no controller
parameter must be changed.
For a refrigerant change go into the parameter menu (press upper button 5 seconds)
Select parameter “r12” (software main switch) with a short press on lower button
Activate parameter r12” with middle button and change the value to 0 (zero)
Conrm the value with a short press on the middle button (the 3 LED’s start ashing)
Go to the parameter o30” (Refrigerant)
Change the value to 3 (stands for R134a), or 17 (R507), or 20 (R407C), or 19 (R404A)
Conrm the value with a short press on the middle button
Select parameter “r12” again
Change the value to 1 (one)
Conrm the value with a short press on the middle button (the 3 LED-signs stop ashing and the con-
densing unit will start if required)
After 20 seconds the display returns to the evaporation temperature in °C, the new refrigerant and all
relevant parameters are changed
R404A *
Room Thermostat control without Pump Down
function
R404A *
Pump Down control
with factory delivered low pressure transmitter
- Connect Room Thermostat to these terminals
- Connect power supply to main switch acc. wir-
ing diagram, located in front door inner side
- Connect power supply to main switch acc. wir-
ing diagram, located in front door inner side
- Increase the Setting of controller Par. c33 (Pump
Down CUT-OUT value):
e.g. Piston : 0,7bar
e.g. Scroll : 1,7bar
Note: To avoid low pressure alarm, the Setting of
c33 should be higher than c75
*: change for other refrigerants following chapters.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss OP-MPHM007NFP00G and is the answer not in the manual?

Danfoss OP-MPHM007NFP00G Specifications

General IconGeneral
BrandDanfoss
ModelOP-MPHM007NFP00G
CategoryHeat Pump
LanguageEnglish

Related product manuals