MG.20.B6.02 – VLT is a registered Danfoss trademark
39
VLT
®
2000 Series
Section 1 Section 2 Section 3
Technical data (continued)
Mains: 3
××
××
× 380-460 V (VLT type 2060: 3
××
××
× 380-415 V)
Meets the international standards, UL/cUL
4
) VLT type 2020 2025 2030 2040 2050 2060
1
)
Constant load (CT):
Output current I
VLT.N
[A] 2.4 2.8 4.0 5.6 7.6 9.7
I
VLT.MAX
[A] (60 s) 3.8 4.5 6.4 9.0 12.2 15.5
Output S
VLT.N
[kVA] 1.91 2.23 3.19 4.46 6.05 6.97
S
VLT.MAX
[kVA] (60 s) 3.06 3.57 5.10 7.14 9.69 11.2
Typical shaft output P
VLT.N
[kW] 0.75 1.1 1.5 2.2 3.0 4.0
Max. cable cross section [mm
2
]444444
Max. motor cable length [m] 40 (with motor coils IP 10:
unscreened cables: 300 m, screened cables: 150 m)
Output voltage U
M
[%] 0-100 in % of mains voltage
Output frequency f
M
[Hz] 0-120 or 0-500; programmable
Rated motor voltage U
M,N
[V] 380/400/415/440/460
Rated motor frequency f
M,N
[Hz] 50/60/87/100
Thermal motor protection during operation Built-in thermal motor protection (electronic)
Switching on the output Unlimited (frequent switching may cause cut-out)
Ramp times [s] 0.1-800
VLT type 2020 2025 2030 2040 2050 2060
1
)
Max. input current I
L,N
[A] 2.3 2.7 3.8 5.3 7.2 9.1
Max. cable cross section [mm
2
]444444
Max. prefuses [A] 16 16 16 16 16 20
Bussmann Fuse type KTN-R 250 V AC
5
) [A] 15 15 15 15 15
Mains supply voltage [V] 3 × 380-460 V ±10% 2060: 3 × 380-415 V ±10%
Mains supply frequency [Hz] 50/60
Power factor/cos. ϕ
1
> 0.90/1.0 at rated load
Efficiency > 0.97 at rated load
Switching on the input times/min. 5
VLT type 2020 2025 2030 2040 2050 2060
1
)
Weight [kg] IP 20 4.0 4.0 4.0 4.2 4.2 4.2
Weight [kg] with built-in RFI filter IP 20 4.6 4.6 4.6 4.8 4.8 4.8
Power loss at max. load CT [W] 58 64 78 114 153 196
Enclosure IP 20 IP 20 IP 20 IP 20 IP 20 IP 20
Vibration test [g] 0.7
Relative humidity [%] Max. 95 IEC 721 (according to VDE 0160)
Ambient temperature [°C] 0 +40, at full load operation
2
)
(according to VDE 0160) [°C] 25 +70, storage/transport
Frequency converter protection Grounding and short-circuit proof
3
)
EMC applied standards Emission EN 55011, Group 1, Class A
(see page 90) CISPR 11 (with RFI and motor filter)
Immunity IEC 1000-4
UL file no. E 134261
1
) VLT 2060 has not been UL approved.
2
) In the range -10 - 0 °C the unit can start and run, but the display indications and certain operating characteristics
will not meet the specifications.
3
) Brake option without protection
4
) Units with built-in RFI filter are not UL-approved.
5
) For the North American market
How to size your VLT

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2010 and is the answer not in the manual?

Danfoss VLT 2010 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2010
CategoryInverter
LanguageEnglish

Related product manuals