Safeguards:
Electronic thermal motor protection against
overload.
Temperature monitoring of the power module
ensures that the adjustable frequency drive
cuts out if the temperature reaches 212 °F
(100 °C). An overload temperature cannot be
reset until the temperature of the power mod-
ule is below 160 °F (70 °C).
The frequency converter is protected against
short-circuits on motor terminals U, V, W.
If an electrical phase is missing, the variable
frequency drive will cut out.
Monitoring of the intermediate circuit voltage
ensures that the variable frequency drive
cuts out if the intermediate circuit voltage is
too low or too high.
The variable frequency drive is protected
against ground fault on motor terminals U, V,
W.
VLT
®
2800 Series
MG.27.A2.22 - VLT
®
is a registered Danfoss trademark 109