Warnings/alarm messages
A warning or an alarm will appear in the display as a
numerical code Err. xx. A warning will be shown on
the display until the fault has been corrected, while an
alarm will continue to flash until the [STOP/RESET]
key is activated.The table shows the various warnings
and alarms, and whether the fault locks the adjustable
frequency drive. After a Trip-locked the line supply is
cut off and the fault is corrected. The line supply is re-
connected and the adjustable frequency drive is reset.
The adjustable frequency drive is now ready. A Trip
can be reset manually in three ways:
1. Via the operating key [STOP/RESET].
2. Via a digital input.
3. Via serial communication.
It is also possible to choose an automatic reset in pa-
rameter 405 Reset function. When a cross appears in
both warning and alarm, this can mean that a warning
comes before an alarm. It can also mean that it is pos-
sible for the user to program whether a warning or an
alarm will appear for a given fault. For example, this is
possible in parameter 128 Motor thermal protection.
After a trip, the motor will coast, and alarm and warning
will blink on the adjustable frequency drive; but if the
fault disappears, only the alarm will blink. After a reset,
the adjustable frequency drive will be ready to start
operation again.
No Description Warning Alarm Trip
locked
2 Live zero error (LIVE ZERO ERROR) X X X
4 Line phase loss (LINE PHASE LOSS) X X X
5 Voltage warning high (DC LINK VOLTAGE HIGH) X
6 Voltage warning low (DC LINK VOLTAGE LOW) X
7 Overvoltage (DC LINK OVERVOLT) X X X
8 Undervoltage (DC LINK UNDERVOLT) X X X
9 Inverter overload (INVERTER TIME) X X
10 Motor overloaded (MOTOR, TIME) X X
11 Motor thermistor (MOTOR THERMISTOR) X X
12 Current limit (CURRENT LIMIT) X X
13 Overcurrent (OVERCURRENT) X X X
14 Ground fault (GROUND FAULT) X X
15 Switch mode fault (SWITCH MODE FAULT) X X
16 Short-circuit (CURR. SHORT CIRCUIT) X X
17 Serial communication timeout (STD BUS TIMEOUT) X X
18 HPFB bus timeout (HPFB TIMEOUT) X X
33 Out of frequency range (OUT FREQ RNG/ROT LIM) X
34 HPFB communication fault (PROFIBUS OPT. FAULT) X X
35 Soft-charge fault (SOFT-CHARGE FAULT) X X
36 Overtemperature (OVERTEMPERATURE) X X
37-45 Internal fault (INTERNAL FAULT) X X
50 AMT not possible X
51 AMT fault re. nameplate data (AMT TYPE.DATA FAULT) X
54 AMT wrong motor (AMT WRONG MOTOR) X
55 AMT timeout (AMT TIMEOUT) X
56 AMT warning during AMT (AMT WARN. DURING AMT) X
99 Locked (LOCKED) X
LED indication
Warning
yellow
Alarm red
Trip-locked yellow and red
WARNING/ALARM 2: Live zero fault
The voltage or current signal on terminal 53 or 60 is
below 50% of the preset value in parameter 309 or 315
Terminal, min. scaling.
VLT
®
2800 Series
98 MG.27.A2.22 - VLT
®