Warnings/alarm messages
A warning or an alarm will appear in the display as a
numerical code Err. xx. A warning will be shown on
the display until the fault has been corrected, while an
alarm will continue to flash until the [STOP/RESET]
key is activated.The table shows the various warnings
and alarms, and whether the fault locks the adjustable
frequency drive. After a Trip-locked the line supply is
cut off and the fault is corrected. The line supply is re-
connected and the adjustable frequency drive is reset.
The adjustable frequency drive is now ready. A Trip
can be reset manually in three ways:
1. Via the operating key [STOP/RESET].
2. Via a digital input.
3. Via serial communication.
It is also possible to choose an automatic reset in pa-
rameter 405 Reset function. When a cross appears in
both warning and alarm, this can mean that a warning
comes before an alarm. It can also mean that it is pos-
sible for the user to program whether a warning or an
alarm will appear for a given fault. For example, this is
possible in parameter 128 Motor thermal protection.
After a trip, the motor will coast, and alarm and warning
will blink on the adjustable frequency drive; but if the
fault disappears, only the alarm will blink. After a reset,
the adjustable frequency drive will be ready to start
operation again.
No Description Warning Alarm Trip
locked
2 Live zero error (LIVE ZERO ERROR) X X X
4 Line phase loss (LINE PHASE LOSS) X X X
5 Voltage warning high (DC LINK VOLTAGE HIGH) X
6 Voltage warning low (DC LINK VOLTAGE LOW) X
7 Overvoltage (DC LINK OVERVOLT) X X X
8 Undervoltage (DC LINK UNDERVOLT) X X X
9 Inverter overload (INVERTER TIME) X X
10 Motor overloaded (MOTOR, TIME) X X
11 Motor thermistor (MOTOR THERMISTOR) X X
12 Current limit (CURRENT LIMIT) X X
13 Overcurrent (OVERCURRENT) X X X
14 Ground fault (GROUND FAULT) X X
15 Switch mode fault (SWITCH MODE FAULT) X X
16 Short-circuit (CURR. SHORT CIRCUIT) X X
17 Serial communication timeout (STD BUS TIMEOUT) X X
18 HPFB bus timeout (HPFB TIMEOUT) X X
33 Out of frequency range (OUT FREQ RNG/ROT LIM) X
34 HPFB communication fault (PROFIBUS OPT. FAULT) X X
35 Soft-charge fault (SOFT-CHARGE FAULT) X X
36 Overtemperature (OVERTEMPERATURE) X X
37-45 Internal fault (INTERNAL FAULT) X X
50 AMT not possible X
51 AMT fault re. nameplate data (AMT TYPE.DATA FAULT) X
54 AMT wrong motor (AMT WRONG MOTOR) X
55 AMT timeout (AMT TIMEOUT) X
56 AMT warning during AMT (AMT WARN. DURING AMT) X
99 Locked (LOCKED) X
LED indication
Warning
yellow
Alarm red
Trip-locked yellow and red
WARNING/ALARM 2: Live zero fault
The voltage or current signal on terminal 53 or 60 is
below 50% of the preset value in parameter 309 or 315
Terminal, min. scaling.
VLT
®
2800 Series
98 MG.27.A2.22 - VLT
®
is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT 2800 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 Series and is the answer not in the manual?

Danfoss VLT 2800 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2800 Series
CategoryDC Drives
LanguageEnglish

Related product manuals