020 Hand operation
(HAND OPERATION)
Value:
Not active (DISABLE) [0]
Active (ENABLE) [1]
Function:
In this parameter you can select whether it should be
possible or not to switch between Auto- and Hand
mode. In Auto mode the adjustable frequency drive is
controlled by external signals whereas the adjustable
frequency drive in Hand mode is controlled via a local
reference directly from the control unit.
Description of choice:
If Not active [0] is selected in this parameter, the Hand
mode function will be inactive. If Active [1] is selected
you can switch between Auto- and Hand mode. For
further information, see the Control Unit section.
024 Userdefined Quick Menu
(user quickmenu)
Value:
Not active (Disable) [0]
Active (Enable) [1]
Function:
In this parameter you can select the standard setup of
the Quick menu key on the control panel and the LCP
2 control panel.
Using this function, in parameter 025 Quick Menu set-
up the user can select up to 20 parameters for the
Quick Menu key.
Description of choice:
If not active [0] is selected, the standard setup of the
Quick Menu key is active.
If Active [1] is selected, the user-defined Quick Menu
is active.
025 Quick Menu setup
(Quick Menu setup)
Value:
[Index 1 - 20] Value: 0 - 999
000
Function:
In this parameter you define which parameters are re-
quired in the Quick Menu when parameter 024 User-
defined Quick Menu is set to Active [1].´
Up to 20 parameters can be selected for the user-de-
fined Quick Menu.
NOTE
Please note that this parameter can only
be set using an LCP 2 control panel. See
Order form.
Description of choice:
The Quick Menu is set up as follows:
1.
Select parameter 025 Quick Menu setup and
press [CHANGE DATA].
2. Index 1 indicates the first parameter in Quick
Menu. You can scroll between the index
numbers using the [+ / -] keys. Select Index
1.
3. Using [< >] you can scroll between the three
figures. Press the [<] key once ad the last
number in the parameter number can be se-
lected using the [+ / -] keys. Set Index 1 to
100 for parameter 100 Configuration.
4. Press [OK] when Index 1 has been set to 100.
5. Repeat steps 2 - 4 until all parameters re-
quired have been set to the Quick Menu key.
6. Press [OK] to complete the Quick Menu set-
up.
If parameter 100 Configuration is selected at Index 1,
Quick Menu will start with this parameter every time
Quick Menu is activated.
Please note that parameter 024 User-defined Quick
Menu and parameter 025 Quick Menu setup are reset
to the factory setting during initialisation.
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
40 MG.27.A2.22 - VLT
®
is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT 2800 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 Series and is the answer not in the manual?

Danfoss VLT 2800 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2800 Series
CategoryDC Drives
LanguageEnglish

Related product manuals