121 Start Function
[0] DC hold during start delay time
[1] DC brake during start delay time
*[2] Coasting during start delay time
[3] Start frequency/voltage clockwise
[4] Start frequency/voltage in reference direction
122 Function at Stop
*[0] Coasting
[1] DC hold
123 Min. Frequency for Activation of Function
at Stop
0.1 - 10 Hz, *0.1 Hz
126 DC Brake Time
0 - 60 s, *10 s
127 DC brake cut-in Frequency
0.0 (OFF) - Par. 202, *OFF
128 Thermal Motor Protection
*[0] No protection
[1] Thermistor warning
[2] Thermistor trip
[3] ETR warning 1
[4] ETR trip 1
[5] ETR warning 2
[6] ETR trip 2
[7] ETR warning 3
[8] ETR trip 3
[9] ETR warning 4
[10] ETR trip 4
130 Start Frequency
0.0 - 10.0 Hz, *0.0 Hz
131 Initial Voltage
0.0 - 200.0 V, *0.0 V
132 DC Brake Voltage
0 - 100% of max. DC brake voltage, *0%
133 Start Voltage
0.00 - 100.00 V, *Dep. on unit
134 Load Compensation
0.0 - 300.0%, 100,0%
135 U/f Ratio
0.00 - 20.00 at Hz, *Dep. on unit
136 Slip Compensation
0 - 150 % * 100 %-500 . +500% of rated slip com-
pensation, *100%
137 DC Hold Voltage
0 - 100% if nax. DC hold voltage, *0%
138 Brake Cut Out Value
0.5 - 132.0/1000.0 Hz, *3.0 Hz
139 Brake Cut In Frequency
0.5 - 132.0/1000.0 Hz, *3.0 Hz
140 Current, Minimum Value
0% - 100% of inverter output current
142 Leakage Reactance X
L
0.000 - xxx.xxx Ω, *Dep- on motor
143 Internal Fan Control
*[0] Automatic
[1] Always switched on
[2] Always switched off
144 Gain AC Brake
1.00 - 1.50, *1.30
146 Reset Voltage Vector
*[0] Off
[1] Reset
References and Limits
200 Output Frequency
Range
*[0] Only clockwise, 0 - 132 Hz
[1] Both directions, 0 - 132 Hz
[2] Counterclockwise only, 0 - 132 Hz
[4] Both directions, 0 - 1000 Hz
[5] Counterclokcwise only, 0 - 1000 Hz
201 Output Frequency Low Limit, f
MIN
0.0 - f
MAX
, *0.0 Hz
202 Output Frequency High Limit, F
MAX
f
MIN
- 132/1000 Hz (par. 200
Output frequency
range
, 132 Hz
203 Reference Range
[0] Min. reference - Max. reference
[1] Analog Input 53 -Max. reference - +Max. refer-
ence
204 Minimum Reference, Ref
MIN
Par. 100 [0]. -100,000.000 - par. 205
Ref
MAX
, *0.000
Hz
Par. 100 [1]/[3], -par. 414
Minimum feedback
- par.
205
Ref
MAX
, *0.000 rpm/par. 416
205 maximum Reference, Ref
MAX
Par. 100 [0]. Par. 204
Ref
MIN
- 1000.000 Hz
, *50.000
Hz
Par. 100 [1]/[3]. Par. 204
Ref
MIN
- Par. 415
Max
Feedback
, *50.000 rpm/par. 416
206 Ramp Type
*[0] Linear
[1] Sin shaped
[2] Sin
2
207 Ramp-up Time 1
0.02 - 3600.00 s, * 3.00 s (VLT 2803 - 2875), *
10.00 (2880 - 2882)
208 Ramp-down Time 1
0.02 - 3600.00 s, * 3.00 s (VLT 2803 - 2875), *
10.00 (2880 - 2882)
209 Ramp-up Time 2
0.02 - 3600.00 s, * 3.00 s (VLT 2803 - 2875), *
10.00 (2880 - 2882)
210 Ramp-down Time 2
0.02 - 3600.00 s, * 3.00 s (VLT 2803 - 2875), *
10.00 (2880 - 2882)
211 Jog Ramp Time
0.02 - 3600.00 s, * 3.00 s (VLT 2803 - 2875), *
10.00 (2880 - 2882)
212 Quick-stop Ramp-down Time
0.02 - 3600.00 s, * 3.00 s (VLT 2803 - 2875), *
10.00 (2880 - 2882)
213 Jog Frequency
0.0 - Par. 202
Output Frequency High Limit, f
MAX
214 Reference Function
*[0] Sum
[1] Relative
[2] External/preset
215-218 Preset reference 1-4
0.0 - 400.0 Hz * 0.0 Hz-100.00% - +100.00%, *
0.00%
219 Catch Up/Slow Down Reference
0.00 - 100% of the given reference, * 0.00%
221 Current Limit, I
LIM
0 - xxx.x% of par. 105, * 160%
223 Warning, Low Current, I
LOW
0.0 - par. 224
Warning: High Current, I
HIGH
, * 0.0 A
224 Warning: High Current, I
HIGH
0 - I
MAX
, * I
MAX
225 Warning: Low Frequency, f
LOW
0.0 - par. 226
Warn.: High frequency, f
HIGH
, *0.0 Hz
226 Warning: High Frequency f
HIGH
If par. 200 = [0]/[1]. Par. 225
f
LOW
- 132 Hz, * 132.0
Hz
If par. 200 [2]/[3]. Par 225
f
LOW
- 1000 Hz, * 132.0
Hz
227 Warning: Low Feedback, FB
LOW
0.0 - 400.0 Hz * 0.0 Hz-100,000.000 - par. 228
Warn.: FB
HIGH
, * -4000.000
228 Warning: High Feedback, FB
HIGH
Par. 227
Warn.: FB
LOW
- 100,000.000, * 4000.000
229 Frequency Bypass, Bandwidth
0 (OFF) - 100 Hz, * 0 Hz
230 - 231 Frequency Bypass 1 - 2
0 - 100 Hz, *0.0 Hz
Inputs and Outputs
302 Terminal 18 Digital Input
[0] No function
[1] Reset
[2] Coasting stop inverse
[3] Reset and coasting inverse
[4] Quick-stop inverse
[5] DC braking inverse
[6] Stop inverse
*[7] Start
[8] Pulse start
[9] Reversing
[10] Reversing
[11] Start Clockwise
[12] Start counterclockwise
[13] Jog
[14] Freeze reference
[15] Freeze output frequency
VLT 2800 Quick Guide 1 Quick Guide
MG.28.M1.02 - VLT
®
is a registered Danfoss trademark
23
1