[16] Speed up
[17] Speed down
[19] Catch up
[20] Slow down
[21] Ramp 2
[22] Preset ref, LSB
[23] Preset ref, MSB
[24] Preset reference on
[25] Thermistor
[26] Precise stop
[27] Precise Start Stop
[31] Selection of Set-up, LSB
[32] Selection of Set-up, MSB
[33] Reset and start
[34 Pulse counter start
303 Terminal 19 Digital Input
See par. 302 * [9] Reversing
304 Terminal 27 Digital Input
[0] No function
[1] Reset
[2] Coasting stop inverse
*[3] Reset and coasting inverse
[4] Quick-stop inverse
[5] DC braking inverse
[6] Stop inverse
[7] Start
[8] Pulse start
[9] Reversing
[10] Reversing
[11] Start Clockwise
[12] Start counterclockwise
[13] Jog
[14] Freeze reference
[15] Freeze output frequency
[16] Speed up
[17] Speed down
[19] Catch up
[20] Slow down
[21] Ramp 2
[22] Preset ref, LSB
[23] Preset ref, MSB
[24] Preset reference on
[25] Thermistor
[26] Precise stop
[27] Precise Start Stop
[31] Selection of Set-up, LSB
[32] Selection of Set-up, MSB
[33] Reset and start
[34 Pulse counter start
305 Terminal 29 Digital Input
See par. 305 * [13] Jog
307Terminal 33 Digital Input
*[0] No function
[1] Reset
[2] Coasting stop inverse
[3] Reset and coasting inverse
[4] Quick-stop inverse
[5] DC braking inverse
[6] Stop inverse
[7] Start
[8] Pulse start
[9] Reversing
[10] Reversing
[11] Start Clockwise
[12] Start counterclockwise
[13] Jog
[14] Freeze reference
[15] Freeze output frequency
[16] Speed up
[17] Speed down
[19] Catch up
[20] Slow down
[21] Ramp 2
[22] Preset ref, LSB
[23] Preset ref, MSB
[24] Preset reference on
[28] Pulse reference
[29] Pulse feedback
[30] Pulse input
[31] Selection of Set-up, LSB
[32] Selection of Set-up, MSB
[33] Reset and start
308 Terminal 53, Analog Input Voltage
[0] No function
*[1] Reference
[2] Feedback
[3] Wobble 309 Terminal 53 Min. Scaling
0.0 - 10.0 V, * 0.0 V
310 Terminal 53 Max. Scaling
0.0 - 10.0 V, * 10.0 V
314 Terminal 60 Analog Input Current
[0] No function
[1] Reference
*[2] Feedback
[10] Wobble
315 Terminal 60 Min. Scaling
0.0 - 20.0 mA, * 4.0 mA
316 Terminal 60 Max. Scaling
0.0 - 20.0 mA, * 20.0 mA
317 Time Out
1 - 99 s * 10 s
318
*[0] No operation
[1] Freeze output frequency
[2] Stop
[3] Jog
[4] Max speed
[5] Stop and trip
319 Analog output terminal 42
[0] No function
[1] External reference min. - max. 0 - 20 mA
[2] External reference min. - max. 4- 20 mA
[3] Feedback min. - max. 0-20 mA
[4] Feedback min. - max. 4- 20 mA
[5] Output frequency 0 - max 0-20 mA
[6] Output frequency 0 - max 4-20 mA
*[7] Output current 0 - I
INV
0-20 mA
[8] Output current 0 - I
INV
4-20 mA
[9] Output power 0-P
M,N
0-20 mA
[10] Output power 0-P
M,N
4-20 mA
[11] Inverter temperature 20-100 °C 0-20 mA
[12] Inverter temperature 20-100 °C 4-20 mA
323 Relay Output 1-3
[0] No function
*[1] Unit ready
[2] Enable/no warning
[3] Running
[4] Running in reference, no warning
[5] Running, no warning
[6] Running in reference range, no warnings
[7] Ready - mains voltage within range
[8] Alarm or warning
[9] Current higher than current limit
[10] Alarm
[11] Output frequency higher than f
LOW
[12] Output frequency lower than f
HIGH
[13] Output current higher than I
LOW
[14] Output current lower than I
HIGH
par. 224
[15] Feedback higher than FB
LOW
[16] Feedback lower than FB
HIGH
par. 228
[17] Relay 123
[18] Reversing
[19] Thermal warning
[20] Local operation
[22] Out of frequency range par. 225/226
[23] Out of current range
[24] Out of feedback range
[24] Mechanical brake control
[25] Control word bit 11
327 Pulse reference/feedback
150 - 67600 Hz, * 5000 Hz
328 Maximum Pulse 29
150 - 67600 Hz, * 5000 Hz
341 Digital/Pulse Output Terminal 46
[0] Unit ready
Par. [0] - [20], see par. 323
[21] Pulse reference
Par. [22] - [25], see par. 323
[26] Pulse feedback
[27] Output frequency
[28] Pulse current
[29] Pulse power
[30] Pulse temperature
342 Terminal 46, max. Pulse Scaling
150 - 10000 Hz, * 5000 Hz
343 Precise Stop Function
*[0] Precise ramp stop
[1] Counter stop with reset
[2] Counter stop without reset
[3] Speed-compensated counter stop
[4] Speed-compensated stop with reset
[5] Speed-compensated stop without reset
344 Counter Value
0 - 999999, * 100000 pulses
349 Speed Comp Delay
0 ms - 100 ms, * 10 ms
Special Functions
400 Brake Function
[0] OFF
[1] Resistor brake
[4] AC brake
[5] Load sharing
1 Quick Guide VLT 2800 Quick Guide
24
MG.28.M1.02 - VLT
®
is a registered Danfoss trademark
1
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Other manuals for Danfoss VLT 2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 and is the answer not in the manual?

Danfoss VLT 2800 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2800
CategoryDC Drives
LanguageEnglish

Related product manuals