Use the following procedure for the control card test:
1. Select control card test.
2. Disconnect the mains voltage and wait until
the light in the display has disappeared.
3. Mount according to drawing and description.
4. Connect the mains voltage.
5. The frequency converter automatically un-
dertakes a test of the control card.
If the frequency converter displays a fault code from
37-45, the control card test has failed. Change the
control card to start up the frequency converter.
If the frequency converter comes into Display mode,
the test is OK. Remove the test connector and the fre-
quency converter is ready for operation. Parameter
620 Operating mode is automatically set to Normal op-
eration [0].
Initialisation [3] is selected if you wish to use the unit's
factory setting.
Procedure for initialisation:
1.
Select Initialisation [3].
2. Disconnect the mains voltage and wait until
the light in the display has disappeared.
3. Connect the mains voltage.
4. An initialisation is performed in all parame-
ters in all Setups, with the exception of pa-
rameters 500 Address, 501 Baudrate,
600-605 Operating data and 615-617 Fault
log.
= factory setting, () = display text, [] = value for use in communication via serial communication port