EasyManuals Logo
Home>Danfoss>DC Drives>VLT 2800

Danfoss VLT 2800 User Manual

Danfoss VLT 2800
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #154 background imageLoading...
Page #154 background image
Technical data, mains supply 3 x 380 - 480 V
According to international standards Type 2805 2807 2811 2815 2822 2830
Output current I
INV.
[A] 1.7 2.1 3.0 3.7 5.2 7.0
(3 x 380-480V)
I
MAX
(60s) [A] 2.7 3.3 4.8 5.9 8.3 11.2
Output power (400 V) S
INV.
[KVA] 1.1 1.7 2.0 2.6 3.6 4.8
Typical shaft output P
M,N
[kW] 0.55 0.75 1.1 1.5 2.2 3.0
Typical shaft output P
M,N
[HP] 0.75 1.0 1.5 2.0 3.0 4.0
Max. cable cross section,
motor
[mm
2
/AWG]
1)
4/10 4/10 4/10 4/10 4/10 4/10
Input current I
L,N
[A] 1.6 1.9 2.6 3.2 4.7 6.1
(3 x 380-480 V)
I
L,MAX
(60s)[A] 2.6 3.0 4.2 5.1 7.5 9.8
Max. cable cross section,
power
[mm
2
/AWG]
1)
4/10 4/10 4/10 4/10 4/10 4/10
Max. pre-fuses
IEC/UL
2)
[A]
20/20 20/20 20/20 20/20 20/20 20/20
Efficiency
3)
[%] 96 96 96 96 96 96
Power loss at 100% load [W] 28 38 55 75 110 150
Weight [kg] 2.1 2.1 2.1 2.1 3.7 3.7
Enclosure
4
type IP 20 IP 20 IP 20 IP 20 IP 20 IP 20
According to international standards Type 2840 2855 2875 2880 2881 2882
Output current I
INV.
[A] 9.1 12 16 24 32.0 37.5
(3 x 380-480V)
I
MAX
(60s) [A] 14.5 19.2 25.6 38.4 51.2 60.0
Output power (400 V) S
INV.
[KVA] 6.3 8.3 11.1 16.6 22.2 26.0
Typical shaft output P
M,N
[kW] 4.0 5.5 7.5 11.0 15.0 18.5
Typical shaft output P
M,N
[HP] 5.0 7.5 10.0 15.0 20.0 25.0
Max. cable cross sec-
tion, motor
[mm
2
/AWG]
1)
4/10 4/10 4/10 16/6 16/6 16/6
Input current I
L,N
[A] 8.1 10.6 14.9 24.0 32.0 37.5
(3 x 380-480 V)
I
L,MAX
(60s)[A] 13.0 17.0 23.8 38.4 51.2 60
Max. cable cross sec-
tion, power
[mm
2
/AWG]
1)
4/10 4/10 4/10 16/6 16/6 16/6
Max. pre-fuses
IEC/UL
2)
[A]
20/20 25/25 25/25 50/50 50/50 50/50
Efficiency
3)
[%] 96 96 96 97 97 97
Power loss at 100% load [W] 200 275 372 412 562 693
Weight [kg] 3.7 6.0 6.0 18.5 18.5 18.5
Enclosure
4
type IP20 IP20 IP20 IP20/
NEMA 1
IP20/
NEMA 1
IP20/
NEMA 1
1. American Wire Gauge. Max. cable cross section is
the largest cable cross section that can be attached to
the terminals. Always observe national and local reg-
ulations.
2. Type gG pre-fuses must be used for installation ac-
cording to IEC rules. If you want to maintain UL/cUL
you must use pre-fuses of the type Bussmann KTN-R
200 V, KTS-R 500 V or Ferraz Shawmut, type ATMR
(max. 30A). The fuses must be placed for protection in
a circuit that is capable of supplying a maximum of
100,000 amps RMS (symmetrical), 500 V maximum.
3. Measured using a 25 m screened/armoured motor
cable with a rated load and rated frequency.
4. IP20 is standard for VLT 2805-2875, whereas
NEMA 1 is an option.
154 MG.27.E2.02 - VLT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT 2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 and is the answer not in the manual?

Danfoss VLT 2800 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2800
CategoryDC Drives
LanguageEnglish

Related product manuals