004 Active Setup
(active Setup)
Value:
Factory Setup (FACTORY SETUP) [0]
Setup 1 (setup 1) [1]
Setup 2 (setup 2) [2]
Setup 3 (setup 3) [3]
Setup 4 (setup 4) [4]
Multi Setup (MULTI SETUP) [5]
Function:
The active parameter Setup is selected here. All pa-
rameters can be programmed in four individual pa-
rameter Setups. Shifts between Setups can be made
in this parameter via a digital input or via serial com-
munication.
Description of choice:
Factory Setup [0] contains the factory-set parameter
values. Setup 1-4 [1]-[4] are four individual Setups
which can be selected as required. Multi Setup [5] is
used where remote-controlled shifts between the four
Setups via a digital input or via serial communication
is required.
005 Programming Setup
(EDIT SETUP)
Value:
Factory Setup (FACTORY SETUP) [0]
Setup 1 (setup 1) [1]
Setup 2 (setup 2) [2]
Setup 3 (setup 3) [3]
Setup 4 (setup 4) [4]
Active Setup (ACTIVE SETUP) [5]
Function:
You can select which Setup you want to programme
during operation (applies both via the control panel
and the serial communication port). It is, for example,
possible to programme Setup 2 [2], while the active
Setup is set to Setup 1 [1] in parameter 004 Active
Setup .
Description of choice:
Factory Setup [0] contains the factory-set data and can
be used as a source of data if the other Setups are to
be reset to a known status. Setup 1-4 [1]-[4] are indi-
vidual Setups that can be programmed freely during
operation. If Active Setup [5] is selected, the program-
ming Setup will be equal to parameter 004 Active
Setup.
NB!
If data is modified or copied to the active
Setup, the modifications have an immedi-
ate effect on the unit's operation.
006 Setup copying
(SETUP COPY)
Value:
No copying (NO COPY) [0]
Copy to Setup 1 from #
(COPY TO SETUP 1) [1]
Copy to Setup 2 from #
(COPY TO SETUP 2) [2]
Copy to Setup 3 from #
(COPY TO SETUP 3) [3]
Copy to Setup 4 from #
(COPY TO SETUP 4) [4]
Copy to all Setups from # (copy to all) [5]
Function:
You can copy from the selected active Setup in pa-
rameter 005 Programming setup to the selected Setup
or Setups in this parameter.
NB!
Copying is only possible in Stop (motor
stopped in connection with a stop com-
mand).
Description of choice:
Copying begins when the required copying function
has been selected and the [OK]/[CHANGE DATA] key
has been pushed. The display indicates when copying
is in progress.
007 LCP copy
(LCP COPY)
Value:
No copying (NO COPY) [0]
Upload all parameters (UPL. ALL PAR.) [1]
Download all parameters (DWNL. ALL PAR.) [2]
Download size-independent parameters
(DWNL.OUTPIND.PAR.) [3]
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark 11
Programming

Other manuals for Danfoss VLT 2805

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2805 and is the answer not in the manual?

Danfoss VLT 2805 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2805
CategoryDC Drives
LanguageEnglish

Related product manuals