Function:
Parameter 007 LCP copy is used if you want to use the
LCP 2 control panel's integral copy function. The func-
tion is used if you want to copy all parameter setups
from one frequency converter to another by moving the
LCP 2 control panel.
Description of choice:
Select Upload all parameters [1] if you want all param-
eter values to be transferred to the control panel. Se-
lect Download all parameters [2] if all parameter values
transferred are to be copied to the frequency converter
to which the control panel is attached. Select Down-
load size-independent par. [3] if you only want to down-
loade the size-independent parameters. This is used
when downloading to a frequency converter with a dif-
ferent rated power size than that from which the pa-
rameter setup originates.
NB!
Upload/download can only be performed
in stop mode. Download can
only be per-
formed to a frequency converter with the
same software version number, see pa-
rameter 626 Database identification no.
008 Display scaling of output frequency
(FREQUENCY SCALE)
Value:
0.01 - 100.00
1.00
Function:
In this parameter, the factor is selected by which the
output frequency is to be multiplied. The value is
shown in the display, provided parameters 009-012
Display readout have been set to Output frequency x
scaling [5].
Description of choice:
Set the required scaling factor.
009 Large display readout
(DISPLAY LINE 2)
Value:
No readout (none) [0]
Resulting reference [%]
(reference [%]) [1]
Resulting reference [unit]
(reference [unit]) [2]
Feedback [unit] (feedback [unit]) [3]
Frequency [Hz] (Frequency [Hz]) [4]
Output frequency x scaling
(frequency x scale) [5]
Motor current [A] (Motor current [A]) [6]
Torque [%] (Torque [%]) [7]
Power [kW] (Power [kW]) [8]
Power [HP] (Power [HP][US]) [9]
Motor voltage [V]
(Motor voltage [V]) [11]
DC link voltage [V]
(DC link voltage [V]) [12]
Thermal load motor [%]
(Motor thermal [%]) [13]
Thermal load [%]
(FC. thermal[%]) [14]
Running hours [Hours]
(RUNNING HOURS]) [15]
Digital input [Bin]
(Digital input[bin]) [16]
Analog input 53 [V]
(analog input 53 [V]) [17]
Analog input 60 [mA]
(analog input 60 [mA]) [19]
Pulse reference [Hz]
(Pulse ref. [Hz]) [20]
External reference [%]
(external ref. [%]) [21]
Status word [Hex] (Status word [hex]) [22]
Heatsink temperature [°C]
(Heatsink temp [°C]) [25]
Alarm word [Hex] (Alarm word [hex]) [26]
Control word [Hex] (Control word [Hex]) [27]
Warning word [Hex]
(warning word [Hex]) [28]
Extended status word [Hex]
(Ext. status [hex]) [29]
Communication option card warning
(COMM OPT WARN [HEX]) [30]
Pulse count
(PULSE COUNTER) [31]
Function:
In this parameter you can select the data value that
you wish to display in the LCP 2 control unit display
line 2 when the frequency converter is switched on.
The display will also be included in the scrollbar in dis-
play mode. In parameters 010-012 Display readout you
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
12 MG.27.A2.02 - VLT
®
is a registered Danfoss trademark

Other manuals for Danfoss VLT 2805

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2805 and is the answer not in the manual?

Danfoss VLT 2805 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2805
CategoryDC Drives
LanguageEnglish

Related product manuals