Technical data, mains supply 1 x 220 - 240 V/3 x 200-240V
According to . international
standards
Type 2803 2805 2807 2811 2815 2822 2822
PD2
2840 2840
PD2
Output current I
INV.
[A] 2.2 3.2 4.2 6.0 6.8 9.6 9.6 16 16
(3 x 200-240V) I
MAX
(60s) [A] 3.5 5.1 6.7 9.6 10.8 15.3 10.6 25.6 17.6
Output power (230
V)
S
INV.
[KVA] 0.9 1.3 1.7 2.4 2.7 3.8 3.8 6.4 6.4
Typical shaft output P
M,N
[kW] 0.37 0.55 0.75 1.1 1.5 2.2 2.2 3.7 3.7
Typical shaft output P
M,N
[HP] 0.5 0.75 1.0 1.5 2.0 3.0 3.0 5.0 5.0
Max. cable cross
section, motor
[mm
2
/AWG]
1)
4/10 4/10 4/10 4/10 4/10 4/10 4/10 4/10 16/6
Input current I
L,N
[A] 5.9 8.3 10.6 14.5 15.2 - 22.0 -
31.0
(1 x 220-240 V)
I
L,MAX
(60s) [A] 9.4 13.3 16.7 23.2 24.3 - 24.3 - 34.5
Input current I
L,N
[A] 2.9 4.0 5.1 7.0 7.6 8.8 8.8 14.7 14.7
(3 x 200-240 V)
I
L,MAX
(60s) [A] 4.6 6.4 8.2 11.2 12.2 14.1 9.7 23.5 16.2
Max. cable cross
section, power
[mm
2
/AWG]
1)
4/10 4/10 4/10 4/10 4/10 4/10 4/10 4/10 16/6
Max. pre-fuses
IEC/UL
2)
[A]
20/20 20/20 20/20 20/20 20/20 20/20 35/35 25/25 50/50
Efficiency
3)
[%] 95 95 95 95 95 95 95 95 95
Power loss at 100%
load
[W] 24 35 48 69 94 125 125 231 231
Weight [kg] 2.0 2.0 2.0 2.0 2.0 3,7 6.0 6.0 18.50
Enclosure
4
type IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20/
NEMA
1
1. American Wire Gauge. Max. cable cross section is
the largest cable cross section that can be attached to
the terminals. Always observe national and local reg-
ulations.
2. Type gG pre-fuses must be used for installation ac-
cording to IEC rules. If you want to maintain UL/cUL
you must use pre-fuses of the type Bussmann KTN-R
200 V, KTS-R 500 V or Ferraz Shawmut, type ATMR
(max. 30A). The fuses must be placed for protection in
a circuit that is capable of supplying a maximum of
100,000 amps RMS (symmetrical), 500 V maximum.
3. Measured using a 25 m screened/armoured motor
cable with a rated load and rated frequency.
4. IP20 is standard for VLT 2805-2875, whereas
NEMA 1 is an option.
VLT
®
2800 Series
90 MG.27.A2.02 - VLT
®
is a registered Danfoss trademark

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2881 and is the answer not in the manual?

Danfoss VLT 2881 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2881
CategoryDC Drives
LanguageEnglish

Related product manuals