36
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT
®
5000 / VLT
®
6000 HVAC / VLT
®
8000 AQUA
A controller node writes [2] (REFERENCE
[UNIT]) to parameter 007 (009), Large Display
Readout, of the VLT.
The controller node sends the following
parameter write request to the VLT.
nvoParamCmd.learn =
LN_LEARN_CURRENT
nvoParamCmd.selector = 7
nvoParamCmd.value[0] = 0
nvoParamCmd.value[1] = 0
nvoParamCmd.value[2] = 0
nvoParamCmd.value[3] = 2
Example 2:
Time 1 - The controller node receives the
following parameter access response from the
VLT.
nviParamResp.learn =
LN_LEARN_CURRENT
nviParamResp.selector = 7
nviParamResp.value[0] = 0
nviParamResp.value[1] = 0
nviParamResp.value[2] = 0
nviParamResp.value[3] = 2
nviParamResp.day = 0
nviParamResp.hour = 0
nviParamResp.minute = 0
nviParamResp.second = 0
nviParamResp.millisecond = 0
Example 3:
Example 4:
A controller node writes 18.0 Hz to VLT
parameter 201, Output Frequency Low Limit.
The conversion index is -1, so the conversion
factor is 0.1.
The controller node sends the following
parameter write request to the VLT.
nvoParamCmd.learn =
LN_LEARN_CURRENT
nvoParamCmd.selector = 201
nvoParamCmd.value[0] = 0
nvoParamCmd.value[1] = 0
nvoParamCmd.value[2] = 0
nvoParamCmd.value[3] = B4 hex (180
decimal)
The controller node receives the following
parameter access response from the VLT.
nviParamResp.learn =
LN_LEARN_CURRENT
nviParamResp.selector = 201
nviParamResp.value[0] = 0
nviParamResp.value[1] = 0
nviParamResp.value[2] = 0
nviParamResp.value[3] = B4 hex
nviParamResp.day = 0
nviParamResp.hour = 0
nviParamResp.minute = 0
nviParamResp.second = 0
nviParamResp.millisecond = 0
A controller node reads the value of parameter
407 (411), Switching Frequency, in the VLT.
The value stored in parameter 407 is 10 kHz.
The conversion index is 2, so the conversion
factor is 100.
The controller node sends the following
parameter read request to the VLT.
nvoParamCmd.learn = LN_RECALL
nvoParamCmd.selector = 407
nvoParamCmd.value[0] = 0
nvoParamCmd.value[1] = 0
nvoParamCmd.value[2] = 0
nvoParamCmd.value[3] = 0
The controller node receives the following
parameter access response from the VLT.
nviParamResp.learn = LN_RECALL
nviParamResp.selector = 407
nviParamResp.value[0] = 0
nviParamResp.value[1] = 0
nviParamResp.value[2] = 0
nviParamResp.value[3] = 64 hex (100
decimal)
nviParamResp.day = 0
nviParamResp.hour = 0
nviParamResp.minute = 0
nviParamResp.second = 0
nviParamResp.millisecond = 0
VLT 5000 parameters are shown in parenthesis, where applicable.

Other manuals for Danfoss VLT 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 and is the answer not in the manual?

Danfoss VLT 5000 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000
CategoryController
LanguageEnglish

Related product manuals