Warnings and alarms
The table gives the different warnings and alarms and
indicates whether the fault locks the adjustable fre-
quency drive. After Trip locked, the mains supply must
be cut and the fault must be corrected. Reconnect the
mains supply and reset the adjustable frequency drive
before being ready. Wherever a cross is placed under
both Warning and Alarm, this can mean that a warning
precedes the alarm. It can also mean that it is possible
to program whether a given fault is to result in a warn-
ing or an alarm. This is possible, e.g. in parameter 404
Brake check. After a trip, alarm and warning will flash,
but if the fault is removed, only alarm will flash. After a
reset, the adjustable frequency drive will be ready to
start operation again.
No. Description Warning Alarm Trip locked
1 10 Volts low (10 VOLT LOW) X
2 Live zero fault (LIVE ZERO ERROR) X X
3 No motor (NO MOTOR) X
4 Phase fault (MAINS PHASE LOSS) X X X
5 Voltage warning high (DC LINK VOLTAGE HIGH) X
6 Voltage warning low (DC LINK VOLTAGE LOW) X
7 Overvoltage (DC LINK OVERVOLT) X X
8 Undervoltage (DC LINK UNDERVOLT) X X
9 Inverter overladed (INVERTER TIME) X X
10 Motor overloaded (MOTOR TIME) X X
11 Motor thermistor (MOTOR THERMISTOR) X X
12 Torque limit (TORQUE LIMIT) X X
13 Overcurrent (OVERCURRENT) X X X
14 Earth fault (EARTH FAULT) X X
15 Switch mode fault (SWITCH MODE FAULT) X X
16 Short-circuit (CURR.SHORT CIRCUIT) X X
17 Standard bus timeout (STD BUS TIMEOUT) X X
18 HPFB bus timeout (HPFB TIMEOUT) X X
19 Fault in EEprom on power card (EE ERROR POWER CARD) X
20 Fault in EEprom on conrol card (EE ERROR CTRL. CARD) X
21 Auto-optimisation OK (AUTO MOTOR ADAPT OK) X
22 Auto-optimisation not OK (AUTO MOT ADAPT FAIL) X
23 Brake test failed (BRAKE TEST FAILED) X X
25 Brake resistor short-circuited (BRAKE RESISTOR FAULT ) X
26 Brake resistor power 100% (BRAKE POWER 100%) X X
27 Brake transistor short-circuited (BRAKE IGBT FAULT) X
29 Heat-sink temperature too high (HEAT SINK OVER TEMP.) X X
30 Motor phase U missing (MISSING MOT.PHASE U) X
31 Motor phase V missing (MISSING MOT.PHASE V) X
32 Motor phase W missing (MISSING MOT.PHASE W) X
33 Quick discharge not OK (QUICK DISCHARGE FAIL) X X
34 Profibus communication fault (PROFIBUS COMM. FAULT) X X
35 Out of frequency range (OUT FREQ RNG/ROT LIM) X
36 Mains failure (MAINS FAILURE) X X
37 Inverter fault (INVERTER FAULT) X X
39 Check parameters 104 and 106 (CHECK P.104 & P.106) X
40 Check parameters 103 and 105 (CHECK P.103 & P.105) X
41 Motor too big (Motor too big) X
42 Motor too small (Motor too small) X
43 Brake fault (BRAKE FAULT) X X
44 Encoder loss (ENCODER FAULT) X X
VLT
®
5000 Series
160 MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.

Table of Contents

Other manuals for Danfoss VLT 5005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5005 and is the answer not in the manual?

Danfoss VLT 5005 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5005
CategoryDC Drives
LanguageEnglish

Related product manuals