Pump
A pump is to run at six different speeds, determined by
shifting between the preset references.
Switch no.:
1
3 4
0 0 0 Preset reference 1
0 0 1 Preset reference 2
0 1 0 Preset reference 3
0 1 1 Preset reference 4
1 0 0 Preset reference 5
1 0 1 Preset reference 6
When switch 1 is active, a setup change to setup 2 is
made.
Start/stop by means of switch 2
1. Choice of Setup, lsb
2. Start/stop
3. Preset reference, lsb
4. Preset reference, msb
The following must be programmed in order shown:
Function:
Parameter: Setting: Data value:
Active Setup 004 Multi-Setup [5]
Digital input, term. 16 300 Choice of Setup, lsb [10]
Digital input, term. 32 306 Preset reference, lsb [6]
Digital input, term. 33 307 Preset reference, msb [6]
Setup copying 006 Copy to Setup 2 from # [2]
Edit Setup 005 Setup 1 [1]
Maximum reference 205 60
Preset reference 1 215 10%
Preset reference 2 216 20%
Preset reference 3 217 30%
Preset reference 4 218 40%
Edit Setup 005 Setup 2 [2]
Maximum reference 205 60
Preset reference 5 215 70%
Preset reference 6 216 100%
All other settings are based on factory settings. How-
ever, motor data (nameplate data) must always be
entered in parameters 102-106.
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 169
Examples of use

Table of Contents

Other manuals for Danfoss VLT 5005

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5005 and is the answer not in the manual?

Danfoss VLT 5005 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5005
CategoryDC Drives
LanguageEnglish

Related product manuals