Display - Status messages
Status messages appear in the 4th line of the display,
see the below example. The status message will be on
the display for approx. 3 seconds.
20.0Hz
SLOW DOWN
FREQUENCY
Start clockwise/anti-clockwise
(START FORW./REV):
Input on digital inputs and parameter data are in con-
flict.
Slow-down (SLOW DOWN):
The output frequency of the adjustable frequency drive
is reduced by the percentage value chosen in param-
eter 219.
Catch-up (CATCH UP):
The output frequency of the adjustable frequency drive
is increased by the percentage value chosen in pa-
rameter 219.
Feedback high (FEEDBACK HIGH):
The FB value is higher than the value set in parameter
228. This message is only shown when the motor is
running.
Feedback low (FEEDBACK LOW):
The FB value is lower than the value set in parameter
227. This message is only shown when the motor is
running.
Output frequency high (FREQUENCY HIGH):
The output frequency is higher than the value set in
parameter 226. This message is only shown when the
motor is running.
Output frequency low (FREQUENCY LOW):
The output frequency is lower than the value set in pa-
rameter 225. This message is only shown when the
motor is running.
Output current high (CURRENT HIGH):
The output current is higher than the value set in pa-
rameter 224. This message is only shown when the
motor is running.
Output current low (CURRENT LOW):
The output current is lower than the value set in pa-
rameter 223. This message is only shown when the
motor is running.
Braking max. (BRAKING MAX):
The brake is functioning.
Optimum braking is effected when the value in param-
eter 402 Braking power limit, KW is exceeded.
Braking (BRAKING):
The brake is functioning.
Ramp operation (REM/ RAMPING):
Remote has been selected in parameter 002 and the
output frequency is changed in accordance with the
ramps set.
Ramp operation (LOCAL/ RAMPING):
Local has been selected in parameter 002 and the out-
put frequency is changed in accordance with the
ramps set.
Running, local control (LOCAL/RUN OK):
Local control has been selected in parameter 002 and
a start command is given on either terminal 18 (START
or LATCHED START in parameter 302) or terminal 19
(START REVERSE parameter 303).
Running, remote control (REM/RUN OK):
Remote control has been selected in parameter 002
and a start command is given on either terminal 18
(START or LATCHED START in parameter 302), ter-
minal 19 (START REVERSE parameter 303) or via the
serial bus.
VLT ready, remote control (REM/UNIT READY):
Remote control has been selected in parameter 002
and Coasting stop inverse in parameter 304, and there
is 0 V on terminal 27.
VLT ready, local control (LOCAL/ UNIT READY):
Local has been selected in parameter 002 and Coast-
ing inverse in parameter 304, and there is 0 V on
terminal 27.
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 157
Messages

Table of Contents

Other manuals for Danfoss VLT 5011

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5011 and is the answer not in the manual?

Danfoss VLT 5011 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5011
CategoryDC Drives
LanguageEnglish

Related product manuals