EasyManuals Logo
Home>Danfoss>DC Drives>VLT 5027

Danfoss VLT 5027 Operating Instructions

Danfoss VLT 5027
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #108 background imageLoading...
Page #108 background image
VLT
®
5000 Series
Programming
made automatically, including the stator resistance
R
S
. A manually entered R
S
must apply to a cold
motor. The shaft performance can be improved by
fine-tuning R
S
and X
S
, see procedure below.
Description of choice:
R
S
can be set as follows:
1. Automatic motor adaptation, where the frequency
converter measures on the motor to determine the
value. All compensations are reset to 100%.
2. The values are stated by the motor supplier.
3. The values are obtained by means of
manual measurements:
-R
S
can be calculated by measuring the
resistance R
PHASE-to-PHASE
between two phase
terminals. If R
PHASE-to-PHASE
is lower than 1-2 ohm
(typically motors >4-5.5 kW, 400 V), a special
ohm-meter should be used (Thomson bridge or
similar). R
S
=0.5xR
PHASE-to-PHASE
4. The factory settings of R
S
, selected by the
frequency converter itself on the basis of the
motor nameplate data, are used.
NB!:
If the setting in parameter 102-109 is changed,
the parameters 110-118 will return to factory
setting. If using special motor characteristics a
change in parameter 102-109 affects parameter 422.
109 Stator reactance
(STATOR REACT.)
Value:
depends on the choice of motor
Function:
After setting motor data in parameters 102-106, a
number of adjustments of various parameters are
made automatically, including the stator reactance
X
S
. The shaft performance can be improved by
fine-tuning R
S
and X
S
, see procedure below.
Description of choice:
X
S
can be set as follows:
1. Automatic motor adaptation, where the frequency
converter measures on the motor to determine the
value. All compensations are reset to 100%.
2. The values are stated by the motor supplier.
3. These values are obtained by means of
manual measurements:
-X
S
can be calculated by connecting a motor to
mains and measuring the phase-to-phase voltage
U
L
as well as the idling current I.
Alternatively, these values can be recorded
during operation in idle running state at the
rated motor frequency f
M,N
, slip compensation
(par. 115) = 0% and load compensation at
high speed (par. 114) = 100%.
4. The factory settings of X
S
, selected by the
frequency converter itself on the basis of the
motor nameplate data, are used.
NB!:
If the setting in parameter 102-109 is changed,
the parameters 110-118 will return to factory
setting. If using special motor characteristics a
change in parameter 102-109 affects parameter 422.
110 Motor magnetizing, 0 rpm
(MOT. MAGNETIZING)
Value:
0-300%
100 %
Function:
This parameter can be used if a different thermal load
on the motor is desired when running at low speed.
Thisparameterisusedinconnectionwith
parameter 111.
Description of choice:
Enter a value stated as a percentage of the
rated magnetizing current.
Too low setting may lead to a reduced torque
on the motor shaft.
111 Min. frequency normal magnetizing
(MIN FR NORM MAGN)
Value:
0.1 - 10.0 Hz
1.0 Hz
Function:
This parameter is used in connection with parameter
110. See drawing in parameter 110.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.51.A9.02 - VLT is a registered Danfoss trademark
107

Table of Contents

Other manuals for Danfoss VLT 5027

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5027 and is the answer not in the manual?

Danfoss VLT 5027 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5027
CategoryDC Drives
LanguageEnglish

Related product manuals