VLT
®
5000 Series
Programming
403 Power monitoring
(POWER MONITORING)
Value:
Off (OFF)
[0]
Warning (WARNING)
[1]
Trip (TRIP)
[2]
Function:
This parameter allows monitoring of the power
transmitted to the brake resistor. The power is
calculated on the basis of the resistor ohm value
(parameter 401), the intermediate circuit voltage and
the resistor running time. If the power transmitted
over 120 sec. exceeds 100% of the monitoring limit
(parameter 402) and Warning [1] has been selected,
a warning will come up on the display. The warning
will disappear if the power goes below 80%. If the
calculated power exceeds 100% of the monitoring
limit and Trip [2] has been selected in parameter 403
Power monitoring, the frequency converter will cut out
while giving an alarm. If power monitoring has been
selected as Off [0] or Warning [1], the brake function
will remain active, even if the monitoring limit has been
exceeded.This may lead to thermal overload of the
resistor. Itisalsopossibletohaveawarningviathe
relay/digital outputs. The typical measuring accuracy
of the power monitoring depends on the accuracy of
the resistor ohmic value (better than ± 20%).
NB!:
The power dissipation during quick
discharge does not form part of the power
monitoring function.
Description of choice:
Select whether this function is to be active (
Warning/Alarm) or inactive (Off).
404 Brake check
(BRAKE TEST)
Value:
Off (OFF)
[0]
Warning (WARNING)
[1]
Trip (TRIP)
[2]
Function:
In this parameter a testing and monitoring function
can be integrated which will give a warning or an
alarm. On power-up it will be tested whether the brake
resistor is disconnected. The test of whether the brake
resistor is disconnected is carried out during braking,
while the test of whether the IGBT is disconnected
is carried out when there is no braking. A warning
or trip disconnects the brake function.
The testing sequence is as follows:
1. If the intermediate circuit voltage is higher than the
brake starting voltage, discontinue the brake check.
2. If the intermediate circuit voltage is unstable,
discontinue the brake check.
3. Carry out a brake test.
4. If the intermediate circuit voltage is lower than the
starting voltage, discontinue the brake check.
5. If the intermediate circuit voltage is unstable,
discontinue the brake check.
6. If the braking power is higher than 100%,
discontinue the brake check.
7. If the intermediate circuit voltage is higher than
the intermediate circuit voltage -2% before the
brake test, discontinue the brake check and
give off a warning or alarm.
8. Brake check OK.
Description of choice:
If Off [0] is selected, this function will still monitor whether
the brake resistor and the brake IGBT short-circuit
during operation, in which case it will give off a warning.
If Warning [1] is selected, the brake resistor and brake
IGBT will be monitored with respect to short-circuiting.
In addition, on power-up it will be checked whether
the brake resistor has been disconnected.
NB!:
A warning in connection with Off [0] or Warning
[1] can only be removed by disconnecting the
mains supply and turning it back on, provided
the fault has been corrected. Please note that in
connection with Off [0] or Warning [1] the frequency
converter will continue even if a fault has been found.
In the case of Trip [2], the frequency converter will
cut out while giving an alarm (trip locked) if the brake
resistor has short-circuited or been disconnected
or if the brake IGBT has short-circuited.
405 Reset function (RESET MODE)
Value:
Manual reset (MANUAL RESET)
[0]
Automatic reset x 1 (AUTOMATIC X 1)
[1]
Automatic reset x 2 (AUTOMATIC X 2)
[2]
Automatic reset x 3 (AUTOMATIC X 3)
[3]
Automatic reset x 4 (AUTOMATIC X 4)
[4]
Automatic reset x 5 (AUTOMATIC X 5)
[5]
Automatic reset x 6 (AUTOMATIC X 6)
[6]
Automatic reset x 7 (AUTOMATIC X 7)
[7]
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.51.A9.02 - VLT is a registered Danfoss trademark
139

Table of Contents

Other manuals for Danfoss VLT 5027

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5027 and is the answer not in the manual?

Danfoss VLT 5027 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5027
CategoryDC Drives
LanguageEnglish

Related product manuals