VLT
®
5000 Series
NonULcompliance
If UL/cUL is not to be complied with, we recommend the above mentioned fuses or:
VLT 5001-5027 200-240 V type gG
VLT 5032-5052 200-240 V type gR
VLT 5001-5062 380-500 V type gG
VLT 5072-5102 380-500 V type gR
VLT 5122-5302 380-500 V type gG
VLT 5352-5552 380-500 V type gR
VLT 5001-5062 525-600 V type gG
Not following the recommendation may result in unnecessary damage of the drive in case of malfunction. Fuses must be designed for
protection in a circuit capable of supplying a maximum of 100000 A
rms
(symmetrical), 500/600 V maximum.