VLT
®
5000 Series
Special
functions
175ZA447.10
Quick discharge
activated
Check 24 Volts
external DC supply
TRIP (RESET)
Q.DISCHARGING FAILED
No 24 Volts external
DC supply
Q.DISCHARGING FAILED
Timeout
Parameter 408 = [1]
Discharge
Discharge completed
POWER IS DISCHARGED
TRIP (RESET)
ALARM:33
ALARM:33
24 Volts external
DC supply OK
Start
Quick discharge
Mains failure/quick discharge with mains
failure inverse
The first column in the table shows Mains failure ,
which is selected in parameter 407. If no function
is selected, the mains failure procedure will not be
carried out. If Controlled ramp-down [1] is selected,
the frequency converter will take the motor down to 0
Hz. If Enable [1] has been selected in parameter 408,
a quick discharge of the intermediate circuit voltage
will be carried out after the motor has stopped.
Usingadigitalinput,itispossibletoactivatemains
failure and/or quick discharge. This is done by
selecting Mains failure inverse on one of the control
terminals (16, 17, 29, 32, 33). Mains failure inverse
is active in the logical 0 situation.
NB!:
The frequency converter can be completely
damaged if the Quick-discharge function
is repeated, using the digital input while
mains voltage is on.
Mains failure par.
407
Quick discharge par. 408 Mains failure inverse digital
input
Function
No function [0] Disable [0] Logical 0 1
No function [0] Disable [0] Logical 1 2
No function [0] Enable [1] Logical 0 3
No function [0] Enable [1] Logical 1 4
[1]-[4] Disable [0] Logical 0 5
[1]-[4] Disable [0] Logical 1 6
[1]-[4] Enable [1] Logical 0 7
[1]-[4] Enable [1] Logical 1 8
Function no. 1
Mains failure and quick discharge are not active.
F
unction no. 2
Mains failure and quick discharge are not active.
F
unction no. 3
The digital input activates the quick discharge function,
regardless of the intermediate circuit voltage level and
regardless of whether the motor is running.
F
unction no. 4
Quick discharge is activated when the intermediate
circuit voltage has dropped to a given value and
the inverters have stopped. See procedure
on previous page.
MG.51.A9.02 - VLT is a registered Danfoss trademark
93

Table of Contents

Other manuals for Danfoss VLT 5027