VLT
®
5000/6000/8000 Series
■
Electrical installation, control leads
Note: The terminals on the control card are detachable.
Connec
t a jumper between terminals 12 +
24 Volt and 27 Coast.
Mount screened cable to external start/stop of control
terminals 12 +24Voltand 18 Start.
■
Pr
ogramming the VLT 5000
The frequency converter is programmed
over the control panel.
Press QUICK MENU
.
The Quick Menu appears in the display. You choose
parameters by means of ↑ and ↓.
Press CHANGE DATA
to change parameter value.
Data values are changed using ↑ and ↓.
Press → or ← to move the cursor. Press OK
to save your parameter setting.
Set the desired language in parameter 001.
Y
ou have six possibilities: English, German,
French, Danish, Spanish, Italian.
Set motor parameters according to the motor plate:
Motor power Parameter 102
Motor voltage Parameter 103
Motor frequency Parameter 104
Motor current Parameter 105
Rated motor speed Parameter 106
Set frequency interval and ramp times.
Min. reference Parameter 204
Max. reference Parameter 205
Ramp up time Parameter 207
Ramp down time Parameter 208
Set Operation site, parameter 002 for Local.
■
Programming the VLT 6000 and VLT 8000 AQUA
The frequency converter is programmed
over the control panel.
Press QUICK MENU
.
The Quick Menu appears in the display. You choose
parameters by means of ↑ and ↓.
Press CHANGE DATA
to change parameter value.
Data values are changed using ↑ and ↓.
Press → or ← to move the cursor. Press OK
to save your parameter setting.
Set the desired language in parameter 001. You have
nine possibilities: English, German, French, Danish,
Spanish, Italian, Swedish, Dutch and Portuguese.
Set motor parameters according to the motor plate:
Motor power Parameter 102
Motor voltage Parameter 103
Motor frequency Parameter 104
Motor current Parameter 105
Rated motor speed Parameter 106
Set frequency interval and ramp times.
Min. reference Parameter 204
Max. reference Parameter 205
Ramp up time Parameter 207
Ramp down time Parameter 208
Relay 1 function Parameter 323
Relay 2 function Parameter 326
■
Motor start
Press START
on VLT 5000 to start the motor or
HAND START on VLT 6000 HVAC to start the motor.
Set motor speed in parameter 003 by VLT 5000.
Set motor speed with the +/- keys on LCP
of VLT 6000 and VLT 8000.
Check if the direction of rotation is as shown
in the display. It can be changed by swapping
two phases of the motor cable.
Press STOP
or OFF/STOP to stop the motor.
MG.56.A2.02 - VLT is a registered Danfoss trademark
28