LCP read-out: Control Card OK.
Disconnect the mains supply and remove the test plug. The green LED on the Control Card will light
up.
If the test fails:
LCP read-out: Control Card I/O failure.
Replace the frequency converter or Control card. The red LED on the Control Card is turned on. Test
plugs (connect the following terminals to each other): 18 - 27 - 32; 19 - 29 - 33; 42 - 53 - 54
Select
Initialization
[2] to reset all parameter values to default settings, except for par. 15-03
Power
Up's
, par. 15-04
Over Temp's
, and par. 15-05
Over Volt's
. The frequency converter will reset during
the next power-up.
Par. 14-22
Operation Mode
will also revert to the default setting
Normal operation
[0].
[0] * Normal operation
[1] Control card test
[2] Initialisation
[3] Boot mode
14-50 RFI Filter
Option: Function:
[0] Off Select
Off
[0] only if the frequency converter is fed by an isolated mains source (IT mains).
In this mode, the internal RFI filter capacitors between chassis and the mains RFI filter circuit are
cut-out to reduce the ground capacity currents.
[1] * On Select
On
[1] to ensure that the frequency converter complies with EMC standards.
15-43 Software Version
Range: Function:
0 N/A* [0 - 0 N/A] View the combined SW version (or ‘package version’) consisting of power SW and control SW.