Mains Supply 3 x 380 - 500 V AC
FC 302
P90K P110 P132 P160 P200
High/ Normal Load* HO NO HO NO HO NO HO NO HO NO
Typical Shaft output at
400 V [kW]
90 110 110 132 132 160 160 200 200 250
Typical Shaft output at
460 V [hp]
125 150 150 200 200 250 250 300 300 350
Typical Shaft output at
500 V [kW]
110 132 132 160 160 200 200 250 250 315
Enclosure IP21 D1 D1 D2 D2 D2
Enclosure IP54 D1 D1 D2 D2 D2
Enclosure IP00 D3 D3 D4 D4 D4
Output current
Continuous
(at 400 V) [A]
177 212 212 260 260 315 315 395 395 480
Intermittent (60 s
overload)
(at 400 V) [A]
266 233 318 286 390 347 473 435 593 528
Continuous
(at 460/500 V) [A]
160 190 190 240 240 302 302 361 361 443
Intermittent (60 s
overload)
(at 460/500 V) [A]
240 209 285 264 360 332 453 397 542 487
Continuous kVA
(at 400 V) [kVA]
123 147 147 180 180 218 218 274 274 333
Continuous kVA
(at 460 V) [kVA]
127 151 151 191 191 241 241 288 288 353
Continuous kVA
(at 500 V) [kVA]
139 165 165 208 208 262 262 313 313 384
Max. input current
Continuous
(at 400 V) [A]
171 204 204 251 251 304 304 381 381 463
Continuous
(at 460/500 V) [A]
154 183 183 231 231 291 291 348 348 427
Max. cable size, mains
motor, brake and load
share [mm
2
(AWG
2)
)]
2 x 70
(2 x 2/0)
2 x 70
(2 x 2/0)
2 x 150
(2 x 300 mcm)
2 x 150
(2 x 300 mcm)
2 x 150
(2 x 300 mcm)
Max. external mains fuses
[A]
1
300 350 400 500 630
Estimated power loss
at 400 V [W]
4)
2369 2907 2634 3357 3117 3914 3640 4812 4288 5517
Estimated power loss
at 460 V [W]
2162 2599 2350 3078 2886 3781 3629 4535 3624 5025
Weight,
enclosure IP21, IP54 [kg]
96 104 125 136 151
Weight,
enclosure IP00 [kg]
82 91 112 123 138
Efficiency
4)
0.98
Output frequency 0 - 800 Hz
Heatsink overtemp. trip 90 °C 110 °C 110 °C 110 °C 110 °C
Power card ambient trip 75 °C
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
Table 5.1
General Specifications
VLT
®
Automation Drive FC 300 Operating Instructions
MG33U402 - Rev. 2013-12-16 95