EasyManuals Logo
Home>Danfoss>DC Drives>VLT AutomationDrive FC 360

Danfoss VLT AutomationDrive FC 360 Application Guide

Danfoss VLT AutomationDrive FC 360
31 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #15 background imageLoading...
Page #15 background image
4 Positioning Control
4.1 Introduction
FC 360 supports positioning control. To use the function,
set parameter 37-00 Application Mode to [2] Position control.
When positioning control is enabled, the frequency
converter runs in VVC
+
control mode. It is important to
perform an AMA with correct motor data prior to
positioning control.
Position feedback signals are sent to FC 360 via MCB102 or
MCB103. 24 V encoder to terminals 32/33 is not supported
in position control mode.
Positioning control in FC 360 provides the following
features:
Supports both relative and absolute positioning.
Can be controlled via digital outs or PROFIBUS.
Supports direct positioning (via PROFIBUS) and
indexed positioning (via digital inputs).
Up to 8 fixed positions.
Supports homing function (without z index).
Uses MCB102 or MCB103 as signal feedback
source.
Supports both software and hardware limit
settings.
4.2
Programming
4.2.1 Preparation
Complete the following tasks before starting the
positioning control.
Check the motor phase
In Hand on mode, set the frequency to a low
positive value. For example, +3 Hz. Make sure the
motor rotates in the positive direction. If it
rotates in the negative direction, exchange the
motor phases.
Remove all signals to inputs.
Select Off mode via the local control panel (LCP
or GLCP).
Initialise the frequency converter in 14-22
Operation Mode.
Perform an AMA.
Set 37-00 Application Mode to [2] Position Control.
Select the feedback source in 37-01 Pos. Feedback
Source and 7-00 Speed PID Feedback Source.
MCB102
Set 17-10 Signal Type and 17-11
Resolution (PPR) according to the specifi-
cation of the actual encoder used.
MCB103
Set 17-50 Poles, 17-51 Input Voltage,
17-52 Input Frequency, and 17-53
Transformation Ratio according to the
specification of the resolver.
Set 17-59 Resolver Interface to [1] Enabled
to enable MCB103 for capture resolver.
Monitor the value of 34-50 Actual Position, rotate
the motor shaft manually in the positive
direction, then 34-50 Actual Position should show
an increasing value. If the value is descending
with an incremental encoder, exchange the
feedback encoder track A+ with B+, and A- with
B-. If no value is displayed, check the wiring of
the encoder.
Set ramp time
Set the activated ramp-up time in 3-41 Ramp 1
Ramp Up Time, 3-51 Ramp 2 Ramp Up Time, 3-61
Ramp 3 Ramp up Time, and 3-71 Ramp 4 Ramp up
Time to be 75% of the minimum value in 37-05
Pos. Ramp Up Time.
Set the activated ramp-down time in 3-42 Ramp 1
Ramp Down Time, 3-52 Ramp 2 Ramp Down Time,
3-62 Ramp 3 Ramp down Time and 3-72 Ramp 4
Ramp Down Time to be 75% of the minimum
value in 37-06 Pos. Ramp Down Time.
Select Auto On mode via LCP or GLCP.
Ensure that there are no alarms.
4.2.2
Basic Settings
Selecting the positioning control source
Select [0] DI or [1] Fieldbus in 37-14 Pos. Ctrl. Source.
Limit settings
Block 1 direction, or set position or velocity limits to
achieve better safety.
Direction block
If necessary, block forward or reverse direction in
37-15 Pos. Direction Block.
Position limit
There are 2 types of position limits: hardware
limits and software limits. Hardware limits are set
by digital inputs. Software limits are set via
parameter settings.
Positioning Control
VLT
®
AutomationDrive FC 360
14 Danfoss A/S © 11/2014 All rights reserved. MG06E102
44

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals