Example
Illustration 54: Location of Switches A53 and A54
5.12 Setting Up RS485 Serial Communication
5.12.1 RS485 Features
RS485 is a 2-wire bus interface compatible with multi-drop network topology. This interface contains the following features:
Ability to select from the following communication protocols:
FC, FC MC, FC option
Modbus RTU
Metasys N2
FLN
BACnet
Functions can be programmed remotely using the protocol software and RS485 connection or in parameter group 8-** Commu-
nications and Options.
Selecting a specic communication protocol changes various default parameter settings to match the specications of the pro-
tocol, making more protocol-specic parameters available.
Option cards for the drive are available to provide more communication protocols. See the option card documentation for in-
stallation and operation instructions.
A switch (BUS TER) is provided on the control card for bus termination resistance.
5.12.2 Conguring RS485 Serial Communication
Procedure
Connect RS485 serial communication wiring to terminals (+) XD2.2 and (-) XD2.3.
- Use shielded serial communication cable.
- Properly ground the wiring. Refer to
5.8.6 Connecting to Ground.
Select the protocol type in parameter 8-30 Protocol.
Select the drive address in parameter 8-31 Address.
Select the baud rate in parameter 8-32 Baud Rate.
AQ357954340588en-000201 / 130R0881 | 93Danfoss A/S © 2020.09
Electrical Installation
VLT® Refrigeration Drive FC 103
Operating Guide