MCD 200 Design Guide
MG.17.C3.02 – VLT is a registered Danfoss trademark 5
MCD 200 Series Overview
General Technical Data
Mains Supply (L1, L2, L3):
MCD 200-xxx-T4-xxx ................................................................................. 3 x 200 VAC ~ 440 VAC (+10% / - 15%)
MCD 200-xxx-T6-xxx ............................................................................... 3 x 200 VAC ~ 575 VAC (+10% / - 15%)
Supply frequency (at start) ................................................................................................................ 45 Hz - 66 Hz
Control Supply (A1, A2, A3):
MCD 200-xxx-xx-CV1 ............................................................................................................ 24 VAC/VDC (± 20%)
MCD 200- xxx-xx-CV3 ........................................... 110-240 VAC (+10% / - 15%) or 380-440 VAC (+10% / - 15%)
Control Inputs
Start Terminal N1 ..................................................................................................... Normally Open, 300 VAC max
Stop Terminal N2 ................................................................................................... Normally Closed, 300 VAC max
Relay Outputs
Main Contactor (Terminals 13 & 14) ................................................................................................. Normally Open
6 A, 30 VDC resistive / 2 A, 400 VAC, AC11
Programmable Relay (Terminals 23 & 24) ......................................................................................... Normally Open
6 A, 30 VDC resistive / 2 A, 400 VAC, AC11
Environmental
Degree of protection MCD 200-007 to MCD 200-055 .................................................................................... IP20
Degree of protection MCD 200-075 to MCD 200-110 .................................................................................... IP00
Operating Temperatures ............................................................................................................... - 10
o
C / + 60
o
C
Humidity ................................................................................................................... 5% to 95% Relative Humidity
Pollution Degree ......................................................................................................................... Pollution Degree 3
Vibration ................................................................................................................... IEC 60068 Test Fc Sinusoidal
4 Hz - 13.2 Hz: ± 1 mm displacement
13.2 Hz – 100 Hz: ± 0.7 g
EMC Emission
Equipment class (EMC) ............................................................................................................................... Class A
Conducted radio frequency emission ................................................................ 0.15 MHz - 0.5 MHz: < 90 dB (µV)
0.5 MHz - 5 MHz: < 76 dB (µV)
5 MHz - 30 MHz: 80-60 dB (µV)
Radiated radio frequency emission ................................................................. 30 MHz - 230 MHz: < 30 dB (µV/m)
230 MHz - 1000 MHz: < 37 dB (µV/m)
This product has been designed for Class A equipment. Use of the product in domestic environments may cause
radio interference, in which case the user may be required to employ additional mitigation methods.
EMC Immunity
Electrostatic discharge .......................................................................... 4 kV contact discharge, 8 kV air discharge
Radio frequency electromagnetic field ............................................................... 0.15 MHz - 1000 MHz: 140 dB (µV)
Rated impulse withstand voltage (Fast transients 5/50 ns) ............................................................ 2 kV line to earth
Rated insulation voltage (Surges 1.2/50 µs – 8/20 ms) ......................................... 2 kV line to earth, 1 kV line to line
Voltage dip and short time interruption ................................................................. 100 ms (at 40% nominal voltage)
Short Circuit
Rated short-circuit current MCD 200-007 to MCD 200-037 ............................................................................ 5 kA
Rated short-circuit current MCD 200-045 to MCD 200-110 .......................................................................... 10 kA

Other manuals for Danfoss VLT MCD 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT MCD 202 and is the answer not in the manual?

Danfoss VLT MCD 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT MCD 202
CategoryController
LanguageEnglish

Related product manuals