Installation Notes:
Make sure that the appropriate input fusing with specified current ratings are
connected between the AC Power Line and the AC drive. A MCC (contactor with
EnglishEnglishmagnetic trip) is recommended between the drive and circuit breaker to
provide a means to disconnect the drive from the power line in the event of a fault.
Make sure that the leads are connected correctly and the drive is properly grounded.
(Ground leads should be at least as the same size as input terminals R, S and T.)
Since the leakage current is larger than 3,5 mA, reinforced, earth is required to ensure
compliance with EN 50178.
Should several units be installed side by side, all the units should be grounded directly
to the ground terminal. Do not form a loop with the ground leads.
Forward
running
When the drive output terminals U, V, and W are connected to the motor terminals U,
V, and W, respectively, the motor will rotate counter-clockwise (viewed from the shaft
of the motor as shown above) when a forward operation command is received ( FWD
lamp is ON).
Make sure that the power source supplies the correct voltage and is capable of
supplying the required current to the drive.
When power is applied to the drive, the internal DC bus charge indicator LED will be
on.
Do not attach or remove wiring or connectors when power is applied to the drive. Do
not attempt to probe signals on the circuit board while the drive is operating.
For single phase applications, the AC input line can be connected to any two of the
three input terminals R, S, T. Note: The drive is not intended for use with single-phase
motors.
To reverse the direction of rotation, interchange the connection of any of the two
motor leads.
Do not connect the AC input to any of the U, V, W terminals, as this will damage the
drive.
English

Table of Contents

Other manuals for Danfoss VLT Micro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro and is the answer not in the manual?

Danfoss VLT Micro Specifications

General IconGeneral
BrandDanfoss
ModelVLT Micro
CategoryMedia Converter
LanguageEnglish

Related product manuals