7.1.3 Status Information (Assembly Instance 154d)
To retrieve status data from the soft starter, use assembly class 04d (0x04), assembly instance 154d (0x9A), attribute 03d (0x03).
7.1.3.1 Bytes 0–1: Starter State
Bits
Function
Details
0
Ready
0 = Not ready
1 = Ready to start
1
Operating mode
0 = Program mode
1 = Operating mode
2
Running
0 = Not ready, ready to start, or tripped
1 = Starting, Running, Stopping, or Jogging
3
Trip
0 = Not tripped
1 = Tripped
4
Jog forward
1 = Jog forward
5
Jog reverse
1 = Jog reverse
6
Reserved
7
Warning
0 = No warning
1 = Warning
8
Ramping
1 = Running (full voltage at the motor)
9
Command source
0 = Remote LCP, digital input, clock
1 = Network
10
Reserved
11
Reserved
12
Reserved
13
Reserved
14
Reserved
15
Temperature limit
0 = Motor operating within thermal capacity (thermal model)
1 = Motor operating above thermal capacity (thermal model)
7.1.3.2 Bytes 2–3: Reserved
Bits
Function
Details
0–15
Reserved
7.1.3.3 Bytes 4–7: Motor Current
Bits
Function
Details
0–31
Motor current
Average rms current across all 3 phases. Measured current is shown as a 32-bit value to 2 decimal places.
10d (0x0A) = 0.10 A
3450d (0xD7A) = 34.50 A
AN353423548483en-000101 / 130R0945 | 19Danfoss A/S © 2020.12
Messaging
EtherNet/IP Card
Installation Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Soft Starter MCD 600 and is the answer not in the manual?

Danfoss VLT Soft Starter MCD 600 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Soft Starter MCD 600
CategoryController
LanguageEnglish

Related product manuals