AS Series Module Manual
9- 16
_9
9.4 RTU Mode
9.4.1 CANopen Mode (AS-FCOPM)
When the function card AS-FCOPM works with an AS series PLC, it supports three kinds of RTU modes, including AS
Remote Communication, CANopen DS301 Mode and Delta Special Driver & AS Remote Mode. Use the knob
FORMAT 1 to turn among three RTU modes.
A. RTU Communication Mode Setup Knob FORMAT 1
FO RM AT 1
Description
0 AS Remote Communication
4 CANopen DS301
8
Delta Special Driver & AS Remote Mode
B. Node ID Setup Knob ID1/ID2
ID1: 0 (recommended)
ID2: 0 (the knob is no function; set up through ISPSoft); see the table below for the knob setting
range.
RTU mode
ID2 setting range
AS Remote Communication
1~F
(by the number of slaves)
Delta Special Driver & AS Remote Mode
1~F
(by the number of slaves)
CANopen DS301
1~F
(if the knob is at 0, the setting range is set by
HWCONFIG)
C. RTU Communication Speed Setup Knob FORMAT 2
Use the knob for setting. You cannot use ISPSoft (HWCONFIG) to set up the communication mode in this
format.
FO RM AT 2
1 2 3 4 5 6 7 8-F
Byte (bps)
10K 20K 50K 125K 250K 500K 1000K NA
Distance (m)
5000
2500
1000
500
250
100
25
NA