AS Series Module Manual
6- 4
Functional specifications
Analog-to-Digital
Conversion
Centigrade (°C) Fahrenheit (°F) Input Impedance
Rated Input Range
*1
Pt100 : -180° C to +800° C
Ni100 : -80° C to +170° C
Pt1000 : -180° C to +800° C
Ni1000 : -80° C to +170° C
JPt100 : -180° C to +500° C
LG-Ni1000 : -50° C to +180° C
Cu50 : -50° C to +150° C
Cu100 : -50° C to +150° C
Pt100 : -292° F to +1,472° F
Ni100:-112° F to +338° F
Pt1000:-292° F to +1,472° F
Ni1000:-112° F to +338° F
JPt100:-292° F to +932° F
LG-Ni1000:-58° F to +356° F
Cu50:-58° F to +302° F
Cu100:-58° F to +302° F
0–300 Ω
0–3000 Ω
Average function
Range: 1-100
Self-diagnosis
Disconnection detection
*1 If the measured temperature exceeds the upper limit, it only shows the maximum value. If the measured
temperature is below the lower limit, it only shows the minimum value.
6.2.2 Profile
38.2
35
88
98.3
1
4
5
2
3
6
04RT D
7
8
9
95
75
7
Unit: mm
Number
Name Description
1 Model Name Model name of the module
2
RUN LED Indicator
Operating status of the module
ON: the module is running.
OFF: the module is not running.
ERROR LED
Indicator
Error status of the module
ON: a serious error exists in the module.