8
Opposite Output
Function
The 6 channels on DTE10P can be set to opposite output, that is, when the output is set to 0, the actual output will be 1.
How to Operate
To set CH1 and CH3 to opposite output, first write 1234H into the address 47F1H and then 0005H into address 4821H to set on CH1 (bit0)
and CH3 (bit2).
CH6 CH5 CH4 CH3 CH2 CH1
Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
Delayed Alarm
Function
When the set condition for alarms is met, the alarm will be enabled after a pre-set period of time.
How to Operate
Set up the time using the table below. Unit: second
CH CH1 CH2 CH3 CH4 CH5 CH6
Address for
delayed alarm
1990H 1991H 1992H 1993H 1994H 1995H
Output Limits
Function
The output is limited between the maximum and minimum percentages.
How to Operate
Set up relevant parameters using the table below.
CH CH1 CH2 CH3 CH4 CH5 CH6
Max. output (%) 1980H 1981H 1982H 1983H 1984H 1985H
Min. output (%) 1988H 1989H 198AH 198BH 198CH 198DH
Note: When the output volume is limited at 20 to 80%, it means the output volume 0 to 100% calculated by the controller is corresponding
to the actual output 20 to 80%.
Programmable Control Time Unit
Function
The unit of programmable control time can be “minute” or “second”.
How to Operate
Write 0 to the address to set the time unit to “minute” (default) or write 1 to set it to “second”.
CH CH1 CH2 CH3 CH4 CH5 CH6
Address for time unit 1978H 1979H 197AH 197BH 197CH 197DH
Input Filter
Function
To avoid unstable PV display due to interferences, DTE10P offers the filter function. Instead of averaging the values, the filter function here
calculate the weighted average value of the “current PV” and “previous PV”.
The filter equation: PV (displayed value) = [previous PV x (filter times – 1) + current PV] / filter times
The bigger the filter times, the bigger the weight of the previous PV, and the smoother the temperature display, which is a good way to