10
INA INB
Content Explanation CH1 CH2 CH3 CH4 CH5 CH6
Max. temperature value
Disabled when higher than
default value
H1010
(H1102)
H1011
(H1202)
H1012
(H1302)
H1013
(H1402)
H1014
(H1502)
H1015
(H1602)
Min. temperature value
Disabled when lower than
default value
H1018
(H1103)
H1019
(H1203)
H101A
(H1303)
H101B
(H1403)
H101C
(H1503)
H101D
(H1603)
Input offset value
-999 ~ +999
Unit: 0.1°C
H1020
(H1104)
H1021
(H1204)
H1022
(H1304)
H1023
(H1404)
H1024
(H1504)
H1025
(H1604)
Proportional band value (Pb)
0 ~ 9,999
Unit: 0.1
H1028
(H1105)
H1029
(H1205)
H102A
(H1305)
H102B
(H1405)
H102C
(H1505)
H102D
(H1605)
Ti value 0 ~ 9,999
H1030
(H1106)
H1031
(H1206)
H1032
(H1306)
H1033
(H1406)
H1034
(H1506)
H1035
(H1606)
Td value 0 ~ 9,999
H1038
(H1107)
H1039
(H1207)
H103A
(H1307)
H103B
(H1407)
H103C
(H1507)
H103D
(H1607)
Integration default
0.0 ~ 100.0%
Unit: 0.1%
H1040
(H1108)
H1041
(H1208)
H1042
(H1308)
H1043
(H1408)
H1044
(H1508)
H1045
(H1608)
Proportional control offset
error value, when Ti = 0
0.0 ~ 100.0%
Unit: 0.1%
H1048
(H1109)
H1049
(H1209)
H104A
(H1309)
H104B
(H1409)
H104C
(H1509)
H104D
(H1609)
Proportional band coefficient
of output 1 and output 2
0.01 ~ 99.99
Unit: 0.01
H1050
(H110A)
H1051
(H120A)
H1052
(H130A)
H1053
(H140A)
H1054
(H150A)
H1055
(H160A)
Dead band of control output
1 & output 2.
-99.9 ~ 999.9
H1058
(H110B)
H1059
(H120B)
H105A
(H130B)
H105B
(H140B)
H105C
(H150B)
H105D
(H160B)
Hysteresis for output 1
0 ~ 9,999
Unit: 0.1%
H1060
(H110C)
H1061
(H120C)
H1062
(H130C)
H1063
(H140C)
H1064
(H150C)
H1065
(H160C)
Hysteresis for output 2
0 ~ 9,999
Unit: 0.1%
H1068
(H110D)
H1069
(H120D)
H106A
(H130D)
H106B
(H140D)
H106C
(H150D)
H106D
(H160D)
Read/write output 1 value Unit: 0.1 %
H1070
(H110E)
H1071
(H120E)
H1072
(H130E)
H1073
(H140E)
H1074
(H150E)
H1075
(H160E)
Read/write output 2 value Unit: 0.1 %
H1078
(H110F)
H1079
(H120F)
H107A
(H130F)
H107B
(H140F)
H107C
(H150F)
H107D
(H160F)
Upper limit for alarm
output
Alarm enabled when
temperature exceeds upper
limit
H1080
(H1110)
H1081
(1210)
H1082
(H1310)
H1083
(H1410)
H1084
(H1510)
H1085
(H1610)
Lower limit for alarm
output
Alarm enabled when
temperature falls below
lower limit
H1088
(H1111)
H1089
(H1211)
H108A
(H1311)
H108B
(H1411)
H108C
(H1511)
H108D
(H1611)
Tuning for upper limit of
analog output
Current (4 ~ 20mA) or
voltage output tuning
H1090
(H1112)
H1091
(H1212)
H1092
(H1312)
H1093
(H1412)
H1094
(H1512)
H1095
(H1612)
Tuning for lower limit of
analog output
Current (4 ~ 20mA) or
voltage output tuning
H1098
(H1113)
H1099
(H1213)
H109A
(H1313)
H109B
(H1413)
H109C
(H1513)
H109D
(H1613)
Input sensor type See “Input” section
H10A0
(H1114)
H10A1
(H1214)
H10A2
(H1314)
H10A3
(H1414)
H10A4
(H1514)
H10A5
(H1614)
Output function for output
1
0: heating
1: cooling
2: proportional output
H10A8
(H1115)
H10A9
(H1215)
H10AA
(H1315)
H10AB
(H1415)
H10AC
(H1515)
H10AD
(H1615)
Output function for output
2
0: heating (default)
1: cooling
2: alarm
H10B0
(H1116)
H10B1
(H1216)
H10B2
(H1316)
H10B3
(H1416)
H10B4
(H1516)
H10B5
(H1616)
Control method
0: PID
1: ON-OFF
2: manual
3: PID programmable
H10B8
(H1117)
H10B9
(H1217)
H10BA
(H1317)
H10BB
(H1417)
H10BC
(H1517)
H10BD
(H1617)
Alarm 1 output mode See “Alarm Output” section
H10C0
(H1118)
H10C1
(H1218)
H10C2
(H1318)
H10C3
(H1418)
H10C4
(H1518)
H10C5
(H1618)
Alarm 2 output mode See “Alarm Output” section
H10C4
(H1518)
H10C5
(H1618)
H10C6
(H1718)
H10C7
(H1818)
Heating/cooling cycle for
output 1
1 ~ 99 seconds
0 = 0.5 second
H10C8
(H1119)
H10C9
(H1219)
H10CA
(H1319)
H10CB
(H1419)
H10CC
(H1519)
H10CD
(H1619)
Heating/cooling cycle for
output 2
1 ~ 99 seconds
0 = 0.5 second
H10D0
(H111A)
H10D1
(H121A)
H10D2
(H131A)
H10D3
(H141A)
H10D4
(H151A)
H10D5
(H161A)
Run/Stop the control
0: stop
H10D8 H10D9 H10DA H10DB H10DC H10DD