11
INA INB
Content Explanation CH1 CH2 CH3 CH4 CH5 CH6
1: executing
2: program stops
3: program pauses
(H111B) (H121B) (H131B) (H141B) (H151B) (H161B)
Status of PID auto-tuning
0: stop
1: executing
H10E0
(H111C)
H10E1
(H121C)
H10E2
(H131C)
H10E3
(H141C)
H10E4
(H151C)
H10E5
(H161C)
Positive/negative
proportional output
0: positive
1: negative (slope)
H10E8
(H111D)
H10E9
(H121D)
H10EA
(H131D)
H10EB
(H141D)
H10EC
(H151D)
H10ED
(H161D)
Other statuses Other statuses
H10F0
Temperature unit
H10F1
Open special
function
(H1234)
H10F2
Return to default
(H1357)
H10F3
Reserved
H10F6
Channel disable
H10F7
Filter times
Communication
specifications
See Table 4
H10F8
Auto ID setup
H10F9
Filter range
H10FA
Baud rate
H10FB
ASCII = 0 RTU =
1
H10FC
8 bits=0
7 bits=1
H10FD
2 stop=0
1 stop=1
LED Status
b0: none; b1: Alarm; b2: °C;
b3: °F; b4: Alarm 1; b5:
OUT2; b6: OUT1; b7: AT
H1124 H1224 H1324 H1424 H1524 H1624
Communication Parameter Setting:
Content
0 1 2 3 4 5 6
Baud rate 2,400bps 4,800bps 9,600bps 19,200bps 38,400bps 57,600bps 115,200bps
Parity bit None (N) Even (E) Odd (O)
Table 4
Error Codes:
The error codes can be read from address H1000 ~ H1007. When the input operation is in normal status, H1000 ~ H1007 are for input
values. When input error occurs (except for stable status and input exceeding the range), DTE will read error codes in H8001 ~ H8002.
H1000 Error description
H8001 EEPROM cannot be written in.
H8002 Input sensor is not connected.
H8003 Group INB is not connected.
Table 5
Analog output current tuning scale: 1μA/scale
Analog output voltage tuning scale: 1mV/scale
Returning to Default Value: Write H1234 into address H10F1 and H1357 into address H10F2. Restart DTE.
Programmable Communication Parameter Setting:
INA INB
Content Explanation CH1 CH2 CH3 CH4 CH5 CH6
Read remaining time of the step Unit: sec H111E H121E H131E H141E H151E H161E
Read remaining time of the step Unit: min H111F H121F H131F H141F H151F H161F
Read the NO. of the current pattern 0 ~ 7 H1120 H1220 H1320 H1420 H1520 H1620
Read the NO. of the current step 0 ~ 7 H1121 H1221 H1321 H1421 H1521 H1621
NO. of start pattern 0 ~ 7 H1122 H1222 H1322 H1422 H1522 H1622
NO. of start step 0 ~ 7 H1123 H1223 H1323 H1423 H1523 H1623
Programmable Parameter Setting:
Content Explanation Pattern 0 Pattern 1 Pattern 2 Pattern 3 Pattern 4 Pattern 5 Pattern 6 Pattern 7
Max. number of steps
in the pattern
0 ~ 7 = N: The pattern
executes from step 0 to N.
H2068 H2069 H206A H206B H206C H206D H206E H206F
Number of cycles of
pattern 0 ~ 7 execution
0 ~ 199: The pattern has
been executed for 1 ~ 200
times
H2070 H2071 H2072 H2073 H2074 H2075 H2076 H2077