20
Quick installation guide for RPI M15A M20A inverters
Setting the AC connection type
1. Whenthedefaultinformationisdisplayed,pressthebutton
ESC
toopenthemainmenu.Otherwise,repeatedlypress
thebutton
ESC
until the main menu is displayed.
20
15
10
5
0
4 8 12 16 20 24
P(w)
Runtime: 8.2Hrs Power: 12103W
On Grid
21. Jun 2013 09:30
E-Today: 47kWh
2. Usethebuttons and to select Settings.
Toconrmyourselection,pressthebutton
ENT
.
E-TodayE-Today
Power Meter
Energy Log
Event Log
Inverter Information
Settings
Operation Data
21. Jun 2013 09:30
Menu
3. Usethebuttons and to select Install Settings.
Toconrmyourselection,pressthebutton
ENT
.
Personal SettingsPersonal Settings
Coefficient SettingsCoefficient Settings
Install Settings
Active/Reactive Power Control
FRT
21. Jun 2013 09:30
Settings
4. Usethebuttons and to select AC Connection.
Tochangethesettings,pressthebutton
ENT
.
Reconnection TimeReconnection Time
AC Connection
RCMU
Grid err. Lock
[
[
] S
]
3P4W
[ ] %/m10
[ ]OFF
6060
21. Jun 2013 09:30
Install Settings
5. Usethebuttons and to select 3P3W.
Toconrmyoursetting,pressthebutton
ENT
.
Reconnection TimeReconnection Time
AC ConnectionAC Connection
RCMU
Grid err. Lock
[
[
] S
]
3P3W
[ ] %/m10
[ ]OFF
6060
21. Jun 2013 09:30
Install Settings
Perdefault,theACconnectiontypeissetto3P4W(3phases+N+PE).OnlyifyouuseanACconnection
with3phases+PE(3P3W),youneedtochangethissetting.ForadescriptionoftheACconnection,see
“Connectingtothegrid(AC)”,p.8.