Chapter 7 Optional AccessoriesMS300
52
7-2 Magnetic Contactor / Air Circuit Breaker and Non-fuse Circuit Breaker
Magnetic Contactor (MC) and Air Circuit Breaker (ACB)
It is recommended the surrounding temperature for MC should be 60°C and that for ACB should be
50°C. In the meanwhile, consider temperature derating for components with ON / OFF switch in
accordance with the ambient temperature of the on-site distribution panel.
115V Models
Frame
Model
Heavy Duty
Input Current (A)
Heavy Duty
Output Current (A)
MC/ACB Selection
(A)
A
VFD1A6MS11ANSAA
6
1.6
11
VFD2A5MS11ANSAA
9.4
2.5
18
C
VFD4A8MS11ANSAA
18
4.8
32
Table 7-6
230V Models
Frame
Model
Heavy Duty
Input Current (A)
Heavy Duty
Output Current (A)
MC/ACB Selection
(A)
A
VFD1A6MS21ANSAA
5.1
1.6
9
VFD2A8MS21ANSAA
7.3
2.8
13
VFD1A6MS23ANSAA
1.9
1.6
9
VFD2A8MS23ANSAA
3.4
2.8
9
VFD4A8MS23ANSAA
5.8
4.8
11
B
VFD1A6MS21AFSAA
5.1
1.6
9
VFD2A8MS21AFSAA
7.3
2.8
13
VFD4A8MS21AFSAA
10.8
4.8
18
VFD4A8MS21ANSAA
10.8
4.8
18
VFD7A5MS23ANSAA
9
7.5
18
C
VFD7A5MS21ANSAA
16.5
7.5
32
VFD11AMS21ANSAA
24.2
11
40
VFD7A5MS21AFSAA
16.5
7.5
32
VFD11AMS21AFSAA
24.2
11
40
VFD11AMS23ANSAA
13.2
11
22
VFD17AMS23ANSAA
20.4
17
32
D
VFD25AMS23ANSAA
30
25
55
E
VFD33AMS23ANSAA
39.6
33
65
VFD49AMS23ANSAA
58.8
49
105
F
VFD65AMS23ANSAA
78
65
130
Table 7-7

Table of Contents

Other manuals for Delta VFD4A8MS23ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD4A8MS23ANSAA and is the answer not in the manual?

Delta VFD4A8MS23ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD4A8MS23ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals