233
06 Protection Parameters (1)
Pr.
Explanation
Settings
Default
06-00
Low Voltage Level
115V / 230V models: 150.0–220.0 V
DC
460V models: 300.0–440.0 V
DC
575V models: 375.0–550.0 V
DC
180.0
360.0
450.0
06-01
Over-Voltage Stall
Prevention
0: Disable
115V / 230V models: 0.0–390.0 V
DC
460V models: 0.0–780.0 V
DC
575V models: 0.0–1000.0 V
DC
380.0
760.0
975.0
06-02
Selection for Over-Voltage
Stall Prevention
0: Traditional over-voltage stall prevention
1: Smart over-voltage stall prevention
0
06-03
Over-Current Stall
Prevention during
Acceleration
Normal load: 0–150%
(100% corresponds to the rated current of the drive)
Heavy load: 0–200%
(100% corresponds to the rated current of the drive)
120
180
06-04
Over-Current Stall
Prevention during
Operation
Normal load: 0–150%
(100% corresponds to the rated current of the drive)
Heavy load: 0–200%
(100% corresponds to the rated current of the drive)
120
180
06-05
Acceleration / Deceleration
Time Selection for Stall
Prevention at Constant
Speed
0: By current acceleration / deceleration time
1: By the first acceleration / deceleration time
2: By the second acceleration / deceleration time
3: By the third acceleration / deceleration time
4: By the fourth acceleration / deceleration time
5: By Auto-acceleration / auto-deceleration
0
06-06
Over-Torque Detection
Selection (Motor 1)
0: No function
1: Continue operation after over-torque detection during
constant speed operation
2: Stop after over-torque detection during constant
speed operation
3: Continue operation after over-torque detection during
RUN
4: Stop after over-torque detection during RUN
0
06-07
Over-Torque Detection
Level (Motor 1)
10–250%
(100% corresponds to the rated current of the drive)
120
06-08
Over-Torque Detection
Time (Motor 1)
0.1–60.0 sec.
0.1

Table of Contents

Other manuals for Delta VFD4A8MS23ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD4A8MS23ANSAA and is the answer not in the manual?

Delta VFD4A8MS23ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD4A8MS23ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals