18
Short circuit current lim-
itaon in baery mode
Depend on the external fuse or breaker
in the upstream of UPS
700VA: 5A
900VA: 6A
1200VA: 16A
1600VA/2200VA:
23A
Short Time withstand
current
50ms
Transfer me 10ms for on-line to baery mode
8.3 Baery
Internal baeries
Specicaons
700VA: 12Vdc – 1 x 12V, 7Ah
900VA: 12Vdc – 1 x 12V, 9Ah
1200VA: 24Vdc – 2 x 12V, 7Ah
1600VA: 24Vdc – 2 x 12V, 7Ah
2200VA: 24Vdc – 2 x 12V, 9Ah
Brand & Reference : LEOCH/DJW12-XX or equivalent
Type
Valve Regulated Lead-Acid (VRLA) Sealed, maintenance-free,
minimum 3-5 year oat service life at 25°C (77°F)
Monitoring Advanced monitoring for earlier failure detecon by indicators
8.4 Environmental and safety
Standards
IEC/EN 62040-1 Safety
IEC/EN 62040-2 Electromagnec Compability EMC
IEC/EN 62040-3 Performance
EMC (Emissions)
CISPR32 Class A
IEC/EN 61000-3-2 Flickers
IEC/EN 61000-3-3 Harmonics
This is a category C2 (Class A) UPS product. In a residenal environ-
ment, this product may cause radio interference, in which case the
user may be required to take addion measures.
EMC (Immunity)
IEC 61000-4-2, (ESD): 4 kV Contact Discharge / 8 kV Air Discharge
IEC 61000-4-3, (Radiated eld): 10 V/m
IEC 61000-4-4, (EFT): 4 kV
IEC 61000-4-5, (Surges): 1 kV Dierenal Mode / 2 kV Common Mode
IEC 61000-4-6, (Electromagnec eld): 10 V
IEC 61000-4-8, (Conducted magnec eld): 30 A/m
Agency markings CE;
Protecon degree IP20