6. Appendices
6.1 Technical specications
5SC 500i 5SC 750i 5SC 1000i 5SC 1500i
Output Power
@ 230 V
500 VA
350 W
750 VA
525 W
1000 VA
700 W
1500 VA
1050 W
AC Input power
•Rated input voltage Single phase 220-240 V
•Input voltage range 184 to 276 V
• Input frequency
range
45 to 55 Hz (50 Hz system), 55 to 65 Hz (60 Hz system)
Output on battery power
•Voltage 220/230/240 V (-10/+6 %)
(1)
•Frequency 50/60 Hz ±0.1 Hz
Battery (sealed lead acid, maintenance free)
•Standard 1 x 12 V
9 Ah
2 x 12 V
7 Ah
2 x 12 V
9 Ah
3 x 12 V
9 Ah
Environment
• Operating
temperature range
0 to 35 °C / 32 to 95 °F
• Storage
temperature range
-15 to +40 °C / 5 to 104 °F
•Relative humidity 0 to 90 % (without condensation)
•Noise level < 40 dBA in normal mode
(1) Adjustable to 220/230/240 V, must be set to the identical AC power source value.
When the appliance is used in EU area, use an external circuit breaker in front of line with rating 16 A,
250 V which is IEC/EN 60898-1 standard compliant;
When the appliance is used in America area, use an external circuit breaker in front of line with rating 20 A,
250 V.
This product is designed for IT power distribution system.
Filter
Transformer
"AVR"
Charger Inverter
Battery
619-00470-02-i (en)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 5SC 500i and is the answer not in the manual?

Eaton 5SC 500i Specifications

General IconGeneral
BrandEaton
Model5SC 500i
CategoryUPS
LanguageEnglish

Related product manuals