Catalog data MN650002EN
Effective February 2019
Deadbreak apparatus connectors
Completing T-body termination
Step 12.
Install STUD into apparatus bushing
ote:N Use only the symmetrical aluminum (STUD635-A)
or copper (STUD635-C) stud in separable splice and
BOL-T applications. Do no use the non-symmetrical
extended length STUD-T.
Ensure unit is de-energized.
Thread the stud into the apparatus bushing unit hand
tight. Refer to Figure 25.
Engage the flats on the stud with a 1/2" wrench and
thread the stud into the bushing an additional 1/4
revolution past hand tight.
Remove any shavings that may have been raised during
the threading procedure.
Install BOL-T connector onto apparatus bushing
Step 13.
Install T-body onto apparatus bushing
Clean and lubricate mating interfaces of apparatus
bushing and T-body with lubricant supplied.
Push T-body onto apparatus bushing ensuring that the
stud on the bushing passes through the hole of the
compression connector. See Figure 26.
Step 14.
Install insulating plug
Clean and lubricate the mating interfaces of T-body and
insulating plug.
Insert insulating plug into back of T-body engaging the
threads of the stud. See Figure 27.
Figure 26. Line illustration of BOL-T connector
installation onto apparatus bushing.
Clean and Lubricate 600 A Interfaces
Apparatus bushing
Concentric neutral
wires
T-body
Figure 27. Line illustration of insulating plug installation.
Thread by Hand
Apparatus bushing
Concentric neutral
wires
Insulating plug
1
/
2
" CROWSFOOT
WRENCH
Figure 25. Line illustration of bushing stud installation.
Symmetrical STUD635-A or STUD635-C
Apparatus bushing
13
600 A 35 kV class BOL-T connector assembly installation instructions MN650002EN February 2019

Other manuals for Eaton 600 A 15 kV class push-OP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 600 A 15 kV class push-OP and is the answer not in the manual?

Eaton 600 A 15 kV class push-OP Specifications

General IconGeneral
BrandEaton
Model600 A 15 kV class push-OP
CategoryCables and connectors
LanguageEnglish

Related product manuals