Eaton 9140 EBM User's Guide S 164201623 Rev C www.eaton.com/powerquality
31
Chapter 4 Maintenance
This section explains how to:
S Care for the UPS and batteries
S Replace the EBM batteries
S Test new batteries
S Recycle used batteries or UPS
UPS and Battery Care
For the best preventive maintenance, keep the area around the UPS
clean and dust‐free. If the atmosphere is very dusty, clean the outside of
the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of
25°C (77°F).
NOTE The batteries in the UPS are rated for a 3–5 year service life. The length of service
life varies, depending on the frequency of usage and ambient temperature. Batteries used
beyond expected service life will often have severely reduced runtimes. Replace batteries at
least every 5 years to keep units running at peak efficiency.
Storing the UPS and Batteries
If you store the UPS for a long period, recharge the battery every
10 months by connecting the UPS to utility power. The batteries charge
to 80% capacity in less than 5 hours. However, it is recommended that
the batteries charge for 48 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date
has expired and the batteries were never recharged, do not use the
UPS. Contact your service representative.