35
F704
Failed inverter soft start
F70C
Inverter undervoltage
F808
Output overload fault
F811
Negative output power
5.Technical data
UPS MODELS
9E6Ki
9E10Ki,
9E10KiXL
9E15Ki
9E20Ki,
9E20KiXL
INPUT
Nominal voltage
[Vac]
220 - 230 - 240
220 - 230 240 / 380 400 - 415
Maximum operating
voltage
[Vac]
276
276 / 478
Nominal frequency
[Hz]
50 - 60
Nominal current
[A]
26
41 / 16
(42 / 20,5 XL)
62 / 22
82 / 28
(83 / 29,5 XL)
BATTERY
Recharge time
(standard versions)
[h]
< 8h for 90% of the charge
Expandability and
nominal voltage of the
Battery Box
180Vdc
240Vdc
240 +
240Vdc
240 +
240Vdc
Charging current
(for XL versions only)
Not
applicable
4,4A
5A
5A
OUTPUT
Nominal voltage
[Vac]
Selectable: 220/230/240
Frequency
[Hz]
Selectable: 50, 60 or auto sensing
Nominal power
[VA]
6000
10000
15000
20000
Nominal power
[W]
4800
8000
12000
16000
Overload: 105% < load <
110%
Bypass line available: activates the bypass
after 5 min, then
continues to work
Bypass line not available: locks after 5 min
Overload: 110% < load <
130%
Bypass line available: activates the bypass
after 1 min, then
locks after 1 min
Bypass line not available: locks after 1 min
Overload: 130% < load <
150%
Bypass line available: activates the bypass
after 10 s, then
locks after 10 s

Other manuals for Eaton 9E15Ki

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 9E15Ki and is the answer not in the manual?

Eaton 9E15Ki Specifications

General IconGeneral
BrandEaton
Model9E15Ki
CategoryUPS
LanguageEnglish

Related product manuals