EasyManuals Logo
Home>Eaton>UPS>9SX 6000VA

Eaton 9SX 6000VA User Manual

Eaton 9SX 6000VA
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
Page 36
5-6kVA EU_EN
7. UPS maintenance
7.5 Replacing the UPS equipped with a HotSwap MBP
The HotSwap MBP allows to service or replace the UPS without interrupting the connected loads.
Refer to the specic user manual for more information about HotSwap MBP.
To remove the UPS:
1. Press any button to activate the menu options. Select Control then Go to Bypass.
2. Check that the UPS is in Bypass mode (Bypass LED should be On).
3. Turn the HotSwap MBP switch to the Bypass position: the red LED on the HotSwap MBP goes On,
indicating that the load is now powered directly from utility power.
4. Set the Normal AC source switch on the HotSwap MBP to the "O" position and wait for 30s.
5. The UPS stops and can now be disconnected.
To reinstall the UPS:
1. Check that the UPS is correctly connected to the HotSwap MBP.
2. Set the Normal AC source switch on the HotSwap MBP to the "I" position.
3. Press the
button to switch On the UPS.
4. Select Control then Go to Bypass (Bypass LED should be On).
5. Turn the HotSwap MBP switch to the Normal position: the red LED on the HotSwap MBP goes Off,
indicating that the load is now powered by the UPS.
6. Select Control then Go back normal.
7. Check that the UPS is in Online mode: the load is now protected by the UPS (Online LED should be
On).
7.6 Recycling the used equipment
Contact your local recycling or hazardous waste center for information on proper disposal of the used
equipment.
Do not dispose of the battery or batteries in a re. Batteries may explode. Proper disposal of batte-
ries is required. Refer to your local codes for disposal requirements.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes.
It may be toxic.
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead acid
batteries and must be disposed of properly. For more information, contact your local recycling/
reuse or hazardous waste center.
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal,
contact your local recycling/reuse or hazardous waste center.

Questions and Answers: