Page 42
5-6kVA EU_EN
9. Specifications
Agency markings CE / C-Tick / cULus
Operating temperature 0 to 40°C (32 to 104°F) in Online mode, with linear derating for altitude
Note: thermal protection switches load to Bypass in case of overheating.
Storage temperature 0 to 40°C (32 to 104°F) with batteries
-15 to 60°C (5 to 140°F) without batteries
Transit temperature -25 to 55°C (-13 to 130°F)
Relative humidity 0 to 95% no condensing
Operating altitude Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000m
Transit altitude Up to 10,000 meters (32,808 ft) above sea level
Audible noise < 45 dBA at 1 meter typical
Table 9. Battery
Internal batteries EBM
Rack / Tower
configuration
5000/6000VA: 180Vdc
15 x 12V, 5Ah
9SXEBM180RT, 9PXEBM180: 180Vdc
2 x 15 x 12V, 5Ah
Fuse 63A 63A
Type Sealed, maintenance-free, valve-regulated, lead-acid,
with minimum 3-year float service life at 25°C (77°F).
Lifetime is reduced above 30 °C.
Monitoring Advanced monitoring for earlier failure detection and warning
Battery port External three-pole SBS75G Black connector on UPS for connection to EBM
EBM battery
cable length
40cm (15.7in)
Table 10. Communication options
Communication bay (1) available independent communication bay for connectivity cards
Compatible connectivity
cards
Network-MS
Modbus-MS
Relay-MS
Communication ports RS-232 (DB9): 1200-19200 bps
USB: 19200 bps
Parallel port (DB15): only for 9PX models
Relay output contacts (4) relay outputs (normally open or normally closed)
Remote On/Off 2 pins jumper (normally open)
Remote Power Off 3 pins jumper (normally open or normally closed)