5 Installation
Installation and Operating Instructions CGLine+ Web-Controller 40071860236 (E) February 2019 www.eaton.com
5.2.2 Push button functions
The CGLine+ Web-Controller has 3 push buttons on the front
plate:
Service button
3
The service pin enables a luminaire search for subsequently
installed luminaires, thus saved luminaires will not be deleted.
Also possible via the service pin to start a function test for
luminaires on all lines.
Functional method:
n
Press the service pin > 1 sec. but < 3 sec.: function test
started for all luminaires
n
Press the service pin > 6 sec.: „only new luminaires“ search
started
1
6 7 8 9
10
2 3
4 5
3
Push buttons:
Service = e.g. starting a FT
System = establish a USB connection on USB2
Reset = hardware reset
4
USB1 host for connecting a USB stick
5
USB2 device for connection to PC
6
PE/N/L 230V 50/60Hz
7
Connection CGLine+ bus line 1-4
8
RS485, currently not in use
9
LAN (RJ45) with LED displays:
Yellow = Link; Green = Traffic
S1/S2 = Block input
In1, In2 = 2 x digital inputs
11, 12, 14, 21, 22, 24 = 2 x relay outputs
Fig. 4. Electrical connections, push buttons and LED dis-
plays