94
INM MTL SUM5 Rev 7
DRAFT - 09 June 2021 DRAFT - 09 June 2021
34 SPECIFICATIONS
Primary power supply
Universal Input Type capable of accepting 85 – 264VAC 50/60Hz or
88 to 300VDC
Optional version (Must be specied at time of order)
19 to 72VDC.
Aux power supplies
Universal Input Type capable of accepting 85 – 264VAC 50/60 Hz or 88 to 300VDC.
Optional version (Must be specied at time of order).
19 to 72VDC.
CAUTION
Power supplies must be fused externally with a 1AT fuse or suitable MCB.
Maximum Power
The maximum power rating for the range of SmartAlarm unit 8 through to 32 channel is 9 Watts
Maximum
Signal Inputs
All inputs are provided with optical isolators capable of withstanding a 1000 volts megger
test to ground.
The standard unit provides an isolated +24VDC as a signal supply voltage and options exist
for 24VDC, 48V DC, 125V AC/DC or 250V AC/DC.
Input response time
The user can select the response time required per channel in the range 1ms to 65S using
the Eaton supplied conguration software.
First-Up discrimination
Better than 10mS.

Table of Contents

Other manuals for Eaton GHG 511

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton GHG 511 and is the answer not in the manual?

Eaton GHG 511 Specifications

General IconGeneral
BrandEaton
ModelGHG 511
CategoryLighting Equipment
LanguageEnglish

Related product manuals