32.4 Multiple Write Request
RTU
START ADDRESS FUNCTION REGISTER /
COIL
ADDRESS
QTY BYTE
COUNT
DATA ERROR
CHECK
STOP
ELAPSED
TIME 3 ½
CHARACTERS
MIN
Y Y Y YY YY
ELAPSED
TIME 3 ½
CHARACTERS
MIN
YY
ELAPSED
TIME 3 ½
CHARACTERS
MIN
32.5 Multiple Write Response
RTU
START ADDRESS FUNCTION REGISTER /
COIL
ADDRESS
QTY ERROR
CHECK
STOP
ELAPSED
TIME 3 ½
CHARACTERS
MIN
Y Y YY YY YY
ELAPSED
TIME 3 ½
CHARACTERS
MIN
32.5.1 Address
Each alarm card is addressed directly. On a typical 32Way SmartAlarm, rst alarm card data is
accessed using node address 1, second alarm card using node address 2 etc. As default the rst
node address starts at 1, this can be modied using the conguration software. Select View -
Advanced then Comms tab and adjust the eld marked “Comms Address Offset”.
First card Node Address = 1 + Comms Address Offset.
Second card Node Address = 2 + Comms Address Offset.
Third card Node Address = 3 + Comms Address Offset.
Comms Address Offset default is 0.
32.5.2 Function
Modbus Function No.
32.5.3 Error Check
This denes the error checking format required, for Modbus RTU this should be set to CRC (Cyclic
Redundancy Check)