Powerware 9910-E33
2700 Watt/3000 VA, 208-240 Vac UPS
Features and Benefits
• 0.9 power factor delivers more real output power in order to power more servers than another UPS
of equivalent VA rating
• Conservers valuable space with 2U rack height
• Hot-swappable batteries and power module allow you to service or replace batteries and
electronics without interrupting power to protected loads or removing the UPS from the rack
• Significantly increases battery service life and gives you advanced warning of the end of useful
battery life with ABM technology
• Prolongs backup time with Extended Battery Modules
• Tested and approved by IBM to assure out-of-box usability
• Includes premium IBM warranty
E33 Model Guide
Model
Number
IBM Number
Power Out
(Watts/VA)
Input
Connection
Output
Connections
Dimensions
(HxWxD, in/mm)
Unit
Weight
(lb/kg)
208-240 Vac; 50/60 Hz auto-sensing
9910-E33
1
42R8065 2700/3000 varies
2
(9) IEC-320-C13,
(1) IEC-320-C19
3.5 (2U) x 17.5 x 24.5/
89 x 440 x 610
89/40.4
Extended Battery Module (EBM)
9910-6643 42R8067 — — —
3.5 (2U) x 17.5 x 24.5/
89 x 440 x 610
100/45.5
1. E33 includes (4) IEC-320-C13 to IEC-320-C14 and (1) IEC-320-C19 to C20 interconnecting cords. 2. E33 input
(mains) connection varies by country. Optional input (mains) connection type IEC-309 P+N+G 32 Amp (FC 2976)
available. See Line Cord Options table.
E33 Battery Runtimes Chart (in Minutes)
Load UPS Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
1350W/1500 VA
15
61
103 146 190
2700W/3000 VA
5
25 49
69 90
Note: This guide provides typical application information. Battery times are approximate and may vary with equipment,