18
CONTINUOUS PILOT BOILER - VR8200A/VR8300A GAS VALVE OPERATING INSTRUCTIONS
1. STOP! Read the safety information on page 17.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. Remove lower front panel.
5. Rotate gas control knob slightly and turn clockwise
to “OFF”
6. Wait ve (5) minutes to clear out any gas. Then smell
for gas, including near the oor. If you smell gas,
STOP! Follow “B” in the safety information on page
17. If you don’t smell gas, go to next step.
7. Find pilot - follow metal tube from gas control. The
pilot is between two burner tubes as shown in Fig.
14.
8. Turn knob on gas control counterclockwise to
“PILOT”
9. Rotate the gas control knob counterclockwise
to “PILOT” Push down and hold the red reset button
while you light pilot burner with a match.
After about one minute, release reset button. Pilot
should remain lit. If it goes out, turn gas control
knob clockwise to OFF To relight, repeat
steps 5-9.
• If button does not pop up when released, stop
and immediately call your service technician or
gas supplier.
• If the pilot will not stay lit after several tries, turn
the gas control knob to “OFF” and call your service
technician or gas supplier.
10.After pilot remains lit when red reset button is
released, turn gas control knob counterclockwise
to “ON.
11. Replace lower front panel.
12. Turn on all electric power to the appliance.
13. Set thermostat to desired setting.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service
is to be performed.
3. Push in gas control knob slightly and turn clockwise
to “OFF” Do not force.
OPERATING YOUR BOILER
AUTOMATIC GAS VALVE
Automatic Gas Valve opens or closes according to heat
requirements of thermostat and temperature limit
control. It closes if pilot goes out. Each individual control
must be operating correctly before any gas can pass
to burners. Any one control can hold gas supply from
burner regardless of demand of any other control.
SAFETY PILOT
Safety Pilot prevents ow of gas to burner if pilot goes
out, or will not ignite.
GAS VALVE SAFETY SHUTDOWN TEST
Ignition system safety shutoff device must be tested
after placing boiler in operation.
For boilers equipped with continuous pilot, with
1.
main burners ring, disconnect the thermocouple
from the gas valve. The gas valve should
immediately shut off main burners and the pilot.
For boilers equipped with intermittent ignition,
2.
with main burners ring, disconnect ignition cable
from intermittent pilot control box. Gas valve
should shut off main burners.
TURN OFF ELECTRIC POWER to boiler before
reconnecting ignition cable, to prevent electric
shock.
RELIGHT
Electric and gas shall be off for 5 minutes before
relighting.
THERMOSTAT
Keep it set at desired room temperature. If windows are
to be opened or heat is not needed, move thermostat
pointer to lower setting.
NOTICE
In event of failure of any component,
system will not operate or will go into
safety lockout. System is completely
self-checking. On every call for heat,
each component must be functioning
properly to permit operation. On safety
lockout system has to be reset by turning
thermostat to lowest setting for one
minute, then back to normal setting.