Installation
15
487 22 52 21 - Cent. 240, 260, 290, GB
Electrical installation.
Electrical Installation is to be carried out by an
authorized electrician.
Switch
Fit a current switch prior to the extractor.
The cable between switch and hydro-extractor
must comply with at least HO5VV-F in
accordance with CEE(13)53 and must hang in a
loop.
Fuse
Fit a current switch prior to the extractor.
Connect the extractor to a separate fuse board.
The motor is fitted with a thermal fuse, which is
why separate motor protection is unnecessary.
Warning
The hydro-extractor must not be connected to a
central timer which disconnects the power
supply at a certain time. The lid cannot be
opened If the current is disconnected while an
extraction cycle is in progress. This means that
there is a risk of the lid being opened by force.
1968
Voltage 200 V 3 AC 230 V 3 AC 400 V 3 AC 415 V 3 AC
Fuse, slow 10A 10A 10A 10A
Cable 4 x 1.5 mm
2
4 x 1.5 mm
2
4 x 1.5 mm
2
4 x 1.5 mm
2
Voltage 115 V 3 AC 200 V 3 AC 208-240 V 3 AC 380 V 3 AC 440 V 3 AC
Fuse, slow 16A 10A 10A 10A 10A
Cable 4 x 2.5 mm
2
4 x 1.5 mm
2
4 x 1.5 mm
2
4 x 1.5 mm
2
4 x 1.5 mm
2
Voltage 200 V 3 AC 230 V 3 AC 400 V 3 AC 415 V 3 AC
Fuse, slow 16A 16A 10A 10A
Cable 4 x 2.5 mm
2
4 x 2.5 mm
2
4 x 1.5 mm
2
4 x 1.5 mm
2
Voltage 115 V 3 AC 200 V 3 AC 208-240 V 3 AC 380 V 3 AC 440 V 3 AC
Fuse, slow 25A 16A 16A 10A 10A
Cable 4 x 6.0 mm
2
4 x 2.5 mm
2
4 x 2.5 mm
2
4 x 1.5 mm
2
4 x 1.5 mm
2
38 litres
58 and 88 litres
50Hz
60 Hz
50 Hz
60 Hz