Grounding
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
The flow computer includes a ground stud on the bottom of the battery box enclosure.
Once you have installed the unit, run a ground wire between the ground stud on the
bottom of the battery box enclosure and a known good earth ground. You route the
ground wire through one of the conduit fittings.
Use stranded copper wire to earth ground and keep the length as short as possible.
Clamp or braze the ground wire to the ground bed conductor (typically a stranded
copper AWG 0000 cable installed vertically or horizontally).
Using a high-wattage soldering iron, tin the wire ends with solder before you insert
them into the chassis ground lug.
Run the ground wire so that any routing bend in the cable has a minimum radius of
30.48 cm (12 inches) below ground and 20.32 cm (8 inches) above ground.
For more information on grounding or if your installation uses cathodic protection, refer to
Site Considerations for Equipment Installation, Grounding, and Wiring (D301452X012).

Other manuals for Emerson ControlWave Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson ControlWave Series and is the answer not in the manual?

Emerson ControlWave Series Specifications

General IconGeneral
BrandEmerson
ModelControlWave Series
CategoryDesktop
LanguageEnglish

Related product manuals